Model TA102A
28
The last A2 alarm option to appear on the display will be the alarm set point (trip level).
If this level is reached or exceeded the A2 alarm outputs will activate. The display
(Figure 52) will indicate the current A2 alarm set point (
10
to
60
in increments of 5).
Press the Mode/Select switch repeatedly, until the desired A2 alarm set point appears
on the display.
60
is the factory default for this selection.
TA102A
0 - 100% LEL
READY
SETUP
SETUP LED
ALARM SETPOINT
A2
FLASHING A2 LED
FLASHING for SETUP
CHECK MODE,
STEADY FOR SETUP MODE
SELECT
MODE/
GENERAL
MONITORS
Figure 52 – A2 Alarm Set Point Option
NOTE -
The
A2
set point cannot be set lower than the current
A1
set point. To
accomplish this, you will need to go through Set-up twice. The
A1
set point should be
set lower than the desired
A2
set point, then re-enter the Setup Mode and set the
A2
set
point.