Model S4000T
42
9.2.2 Mechanical Specifications
Length:
6.4 inches (161mm)
Height:
3.4 inches (86mm)
Width:
4.1 inches (104mm)
Weight:
5.5 lbs. (2.5 kg)
Mounting Holes:
5.0 inches (127mm) (center to center)
9.2.3 Electrical Specifications
Input Power:
24 VDC nominal, 20 to 36 VDC, 350mA max.
Relay Ratings:
8A @ 250 VAC/8A @ 30 VDC resistive max.
(3x) SPDT - Warning, Alarm & Fault
Analog Signal:
0-20mA (650 ohms max. load)
Malfunction 0mA
Gas Check
1.5mA
Setup mode
1.5mA
Calibration 1.5mA
Zero reading
4mA
±
0.2mA
0-100% scale
4-20mA
Over-range
20-22mA
Status Indicators:
Three-digit digital display with gas concentration, Warn and
Alarm LED’s, calibration prompts, fault codes, and setup
options
RS-485 Output:
Dual Redundant Modbus RTU, suitable for linking up to 128
units or up to 247 units with repeaters
Baud Rate:
2400, 4800, 9600, or 19200 BPS
Faults Monitored:
Open
AO,
calibration error, sensor heater error, low DC
supply, EEPROM, EPROM, setup error, gas check time
exceeded, switch error.
Cable Requirements:
3-wire shielded cable. Max. distance between S4000T and
power source @ 24 VDC nominal
AWG
FEET
METERS
14 2000 610
16
1550
410
18 1050 320
20
650
200
Figure 37 24VDC Cable Lengths
Max. distance for analog output (650 ohms max):
AWG
FEET
METERS
14 9000 2740
16
5200
1585
18 3800 1160
20
2400
730
Figure 38 Analog Output Cable Lengths