Operation
Volatile liquids are not supplied by General Monitors.
Below is a list of volatile liquids and the volume required
(in microliters) to produce 50% LEL in the 3 liter chamber.
Acetaldehyde
137
Acetic Acid
140
Acetone
113
Acetonitrile
96
Acrylonitrile
121
Amyl Acetate
100
Amylamine
156
Benzene
71
Butyl Acetate
137
Butyl Acylate
132
Butyl Alcohol
79
sec-Butyl Alcohol
95
tert-Butyl Alcohol
139
Butyl Cellosolve
88
Butyraldhyde
103
Cyclohexane
86
Decane
96
Diethyl Ketone
104
Diisobutyl Ketone
82
Dimethylformamide
104
p-Dioxane
105
Dodecane
84
Ether, Ethyl
120
Ethanol (Ethyl Alcohol)
119
Ethyl Acetate
120
Ethyl Amine
140
Ethyl Benzene
75
Ethylene Oxide
91
Gasoline 100 Octane
107
Heptane, Normal
94
Hexane, Normal
87
Isopentane
100
Isoprene
92
Isopropyl Alcohol
94
Isopropyl Ether
121
JP-4 Jet Fuel
183
Laktane
76
Methanol
149
Methyl Ethyl Ketone (MEK)
77
Methyl Metacrylate
112
Naptha (Petroleum Ether)
94
Octane
100
Pentane, Normal
106
Propanol
115
2-Propanol
93
Propyl Acetate
108
Propylamine
101
Propylbenzene
68
Propylene Oxide
99
Styrene
63
Tetradecane
80
Tetrahydrofuran
100
Tetrahydrofurfuryl Alcohol
89
Toluene
71
1,1,1-Trichlorethane
459
Trichloroethylene
440
Triethylamine
103
Vinyl Acetate
147
Vinyl Ethyl Ether
100
o-Xylene
67
p-Xylene
82
Xylenes
83
4.2
Digital Display Codes
The following codes will appear on the dis-
play when the unit is placed in a mode other
than the normal operating mode.
SU
Start-Up
- - (steady)
Magnetic Switch Activated
- - (flashing) Test Gas Mode
AC
Automatic Calibration
CP
Calibration in Progress
CC
Calibration is Complete
F1
Failed to Zero during calibration
F2
Failed to complete the calibration
F3
Failed to Span during calibration
F4
Sensor Reference Bead Error
F5
Sensor Active Bead Error
F6
Low Supply Voltage
F7
EEPROM Verification Failure
F8
Negative Zero Drift
F9
Calibration check period exceeded
When the unit is in the normal operating
mode, the display will indicate the presence of
combustible gas in percent of the Lower Ex-
plosive Level (% LEL). The range of detec-
tion is from 0 to 99% LEL.
99 (
flashing
) Over-Range, a gas concentration
exceeding 100% LEL is present.
SU
This is displayed for about fifty seconds
during start-up and after a Fault condition
has been corrected.
- -
Appears on the display when the magnet
has been properly positioned over the
GMI Logo and when the Test Gas
Mode can be or has been entered.
14
GENERAL MONITORS
Model S104