M02 Digital Indicator
54
The following items are two bytes and are available to read and write
(write code 0x06
,
read code 0x03
)
40007
0006
Zeroing(zeroing when write in non-zero value)
40008
0007
Automatically zeroing when power on
(
0
:
OFF
;
1
:
ON
)
40009
0008
Zero tracking range
(
0-9d
)
40010
0009
Stable range
(
1-9d
)
40011
0010
Zeroing range
(
0%-99%
)
40012
0011
Digit filter parameters
(0-9)
40013
0012
Stability filter series
(0-9)
40014
0013
AD sample rate
:
0:15/s 1:30/s 2:60/s 3
:
120 /s
4:480/s
5:960/s
40015~
40018
0014~
0017
Reserved
40019
0018
Decimal point place
(
0:0bit,1:1bit,2:2bits,3:3bits,4:4bits
)
40020
0019
Minimum division
(
1/ 2/ 5/ 10/ 20/ 50
)
The following items are available to read and write
(writing code 0x10
,
read code 0x03
)
40021
0020
Maximum capacity
(
max.capacity≤mini.division×
100000
)
40022
0021