4
Chapter ii Installation and Wiring
2.1 Connecting Power cables to the controller
The packaging controller uses 220V, 50Hz AC power supply
with protective ground.The connection is as shown below:
2.2 Sensor Connection
Gmt-h1 mold block shall be externally connected with resistance
strain bridge sensor, and the sensor shall be connected to the module as
shown below.
When a four-wire sensor is selected, the SN+ and EX+ of the
module must be short-circuited, and the SN- and EX- must be
short-circuited.Each port of the sensor connection terminal is assigned to:
port
EX+
SN+
EX-
SN-
SIG+
SIG-
SHLD
6 wire
positive Sensor
positive
negative sensor
negative
signal
positive
Signal
negative
Shielding
wire
4 wire
system
positive
negative
signal
positive
Signal
negative
Shielding
wire
Matters needing attention:
1.
Because the sensor output signal is more sensitive to electronic noise
analog signal, so sensor wiring should be shielded cable, and laid separately
with other cables, especially away from the AC power supply;
2.
For the transmission distance is short and the temperature change is not
large occasions or precision requirements are not high occasions can choose
Summary of Contents for GMT-H1
Page 1: ...GMT H1 Operating instruction V E R 0 1 0 0 0 2...
Page 10: ...7...
Page 11: ...8 Chapter three menu overview...
Page 13: ...10 1 Switch parameter value...
Page 45: ...42 Chapter 11 Product size...