background image

 

STANDBY 

PRIME

 

SG010 

SG015 

SG010 

SG015 

GENERATOR OUTPUT VOLTAGE/KW-60Hz 

 

NG/LP   Rated AMP  NG/LP    Rated AMP  NG/LP   Rated AMP 

NG/LP    Rated AMP

  120/240V, 1-phase, 1.0 pf 

 

10     41.7 

15 

  62.5 

7.2    30.0 

11 

  45.8

  120/208V, 3-phase, 0.8 pf 

 

10 

  34.7 

15 

  52.1 

7.2    25.0 

11 

  38.2

  120/240V, 3-phase, 0.8 pf 

 

10 

  30.1 

15 

  45.2 

7.2    21.7 

11 

  33.1

  277/480V, 3-phase, 0.8 pf 

 

10 

  15.1 

15 

  22.6 

7.2    10.8 

11 

  16.6

 
MOTOR STARTING KVA
  Maximum at 35% instantaneous voltage dip 
   

with standard alternator; 60 hz 

 

20   

 

29 

 

 

20   

 

29

                               
FUEL 

 

  Fuel consumption—60 hz—100% Load 

 

N.G.    L.P. 

N.G.   

L.P. 

N.G.    L.P. 

N.G.   

L.P.

   

ft.

3

/hr. 

185    77 

265    110 

145    60 

204   

85

   

m

3

/hr. 

5.2 

  2.2 

7.5 

 

3.1 

4.1    1.7 

5.8   

2.4

 
COOLING
  Coolant capacity 

System  lit.(US gal.) 

 6.6 (1.75) 

 6.6 (1.75)  

 6.6 (1.75) 

 6.6 (1.75)

   

Engine  lit.(US gal.) 

 0.9 (0.25) 

 0.9 (0.25)  

 0.9 (0.25) 

 0.9 (0.25)

   

Radiator  lit.(US gal.) 

 6.6 (1.75) 

 6.6 (1.75)  

 6.6 (1.75) 

 6.6 (1.75)

  Coolant flow/min. 

60 hz  lit.(US gal.) 

  25 (6.6)  

  25 (6.6)   

 25 (6.6)  

 25 (6.6)

  heat rejection to coolant 

60 hz BTU/hr. 

  48,000  

  72,000   

  35,000  

  53,000

  Cooling air flow 

60 hz m

3

/min. (cfm) 

 40 (883)  

 40 (883)  

 40 (883)  

 40 (883)

 
COMBUSTION AIR REQUIREMENTS
  Flow at rated power  

60 hz m

3

/min. (cfm) 

  0.8 (29)  

  1.2 (41)   

 0.6 (22)  

 0.9 (32)

EXHAUST
  Exhaust flow at rated output 

60 hz m

3

/min. (cfm) 

 2.7  (96)  

 3.9 (137)  

 2.1 (75)  

 3.0 (32)

  Max. recommended back pressure 

Kpa (hg) 

 5.0  (1.5") 

 5.0  (1.5")  

 5.0  (1.5") 

 5.0  (1.5") 

  Exhaust temp. at rated output  

 

o

C (

o

F) 

 593 (1100) 

 621 (1150) 

 566 (1050) 

 593 (1100)

  Exhaust outlet size 

             N.P.T. (female) 

  1.5"   

  1.5"   

  1.5"   

  1.5"

ENGINE
  Rated RPM 

60 hz 

  1800   

  1800   

  1800   

  1800

  hP at rated KW 

60 hz 

 

15   

 

23 

 

 

11   

 

17

  Piston speed 

60 hz m/min. (ft./min.) 

  295 (969) 

 295 (969)  

 295 (969) 

 295 (969) 

  BMEP (psi) 

60 hz - psi 

 

77   

  116   

 

55   

 

85

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
  Temperature 
   

-3% for every 10

o

C above - °C 

 

40   

 

25 

 

 

40   

 

25

   

-1.5% for every 10

o

F above - °F 

  104   

 

77 

 

  104   

 

77

  Altitude
   

-3% for every 300 m above - m 

  913   

  150   

  913   

  150

   

-3% for every 1000 ft. above - ft. 

  3000   

  500   

  3000   

  500

OPERATING DATA

 

SG010 / SG015

Summary of Contents for SG010

Page 1: ...HGEAR AND ACCESSORIES Long life and reliability is synonymous with GENERAC POWER SYSTEMS One reason for this confidence is that the GENERAC product line includes its own transfer systems accessories switchgear and controls for total system compatibility INNOVATIVE DESIGN PROTOTYPE TESTING are key components of GENERAC S success in IMPROVING POWER BY DESIGN Butitdoesn tstopthere Totalcommitmenttoco...

Page 2: ...ATTERY CHARGE ALTERNATOR 15 Amps at 12 V STARTER MOTOR 12 V RECOMMENDED BATTERY 1 12 V 530 CCA 26F GROUND POLARITY Negative APPLICATION ENGINEERING DATA GENERATOR FEATURES Rating definitions Standby Applicable for supplying emergency power for the duration of the utility power outage No overload capability is available for this rating All ratings in accordance with BS5514 ISO3046 and DIN6271 Prime...

Page 3: ...6 1 75 Coolant flow min 60 Hz lit US gal 25 6 6 25 6 6 25 6 6 25 6 6 Heat rejection to coolant 60 Hz BTU hr 48 000 72 000 35 000 53 000 Cooling air flow 60 Hz m3 min cfm 40 883 40 883 40 883 40 883 COMBUSTION AIR REQUIREMENTS Flow at rated power 60 Hz m3 min cfm 0 8 29 1 2 41 0 6 22 0 9 32 EXHAUST Exhaust flow at rated output 60 Hz m3 min cfm 2 7 96 3 9 137 2 1 75 3 0 32 Max recommended back press...

Page 4: ... Solenoid Low Coolant Temperature Secondary Fuel Regulator N G and L P Low Fuel Pressure Alarm Stainless Steel Flexible Exhaust Connection Battery Charge Alternator Battery Cables Battery Tray Vibration Isolation of Unit to Mounting Base 12 Volt Solenoid Activated Starter Motor Air Cleaner Fan Guard Control Console Radiator Duct Adapter OPTIONAL FUEL ACCESSORIES Flexible Fuel Lines L P Liquid With...