Generac Power Systems RTSN100J3S Owner'S Manual Download Page 6

 4 

Section 2 — Installation

RTS “HS” Type Transfer Switch

Solderless, screw-type terminal lugs are standard.

The conductor size range is as follows:

Conductor sizes must be adequate to handle the max-
imum current to which they will be subjected; based 
on the 75°C column of tables, charts, etc. used to size 
conductors. The installation must comply fully with 
all applicable codes, standards and regulations.

Before connecting wiring cables to terminals, remove 
any surface oxides from the cable ends with a wire 
brush. All power cables should enter the switch next 
to transfer mechanism terminals. If ALUMINUM con-
ductors are used, apply corrosion inhibitor to con-
ductors. Tighten terminal lugs to the torque values as 
noted on the decal located on the inside of the door. 
After tightening terminal lugs, carefully wipe away 
any excess corrosion inhibitor.

All power cables should enter the switch next to the 
transfer mechanism terminals.

  Use a torque wrench to tighten the conductors, 

being sure not to overtighten, or damage to 
the switch base could occur. If undertightened, 
a loose connection would result, causing excess 
heat which could damage the switch base.

Connect power source load conductors to clearly 
marked transfer mechanism terminal lugs as fol-
lows:

1.  Connect UTILITY (NORMAL) power source cables 

to switch terminals N1, N2, (N3).

2.  Connect EMERGENCY (STANDBY) source power 

cables to transfer switch terminals E1, E2, (E3).

3.  Connect customer LOAD leads to switch termi-

nals T1, T2, (T3).

4. Connect neutral conductors of UTILITY, 

EMERGENCY and customer LOAD to the neutral 
block.

Conductors must be properly supported, of approved 
insulative qualities, protected by approved conduit, 
and of the correct wire gauge size in accordance with 
applicable codes.

Be sure to maintain proper electrical clearance 
between live metal parts and grounded metal. Allow 
at least 1/2 inch for 100-400 amp circuits.

2.5  

CONNECTING START CIRCUIT
WIRES

Control system interconnections consist of UTILITY 
1 and 2, and leads 23 and 194. Control system 
interconnection leads must be run in a conduit that 
is separate from the AC power lead. Recommended 
wire gauge sizes for this wiring depends on the length 
of the wire, as recommended below:

2.6   AUXILIARY CONTACTS

If desired, there are Auxiliary Contacts on the transfer 
switch to operate customer accessories, remote advi-
sory lights, or remote annunciator devices. A suitable 
power source must be connected to the COMMON (C) 
terminal. See Figure 2.3.

Contact operation is shown in the following chart:

NOTE:

Auxiliary Contacts are rated 10 amps at 125 or 
250 volts AC. DO NOT EXCEED THE RATED 
VOLTAGE AND CURRENT OF THE CONTACTS.

Figure 2.3 – Auxiliary Contacts

S

ide views shown in Utility position

  MAXIMUM WIRE LENGTH 

RECOMMENDED WIRE

  

SIZE

 

460 feet (140m) 

No. 18 AWG.

 

461 to 730 feet (223m) 

No. 16 AWG.

  731 to 1,160 feet (354m) 

No. 14 AWG.

  1,161 to 1,850 feet (565m) 

No. 12 AWG.

 

Switch Position

  

Utility 

Standby

  Common to Normally Open 

Open 

Clo

s

ed

  Common to Normally Clo

s

ed Clo

s

ed Open

 

Switch Rating 

Wire Range

 

400A 

(1) #4-600 MCM or

 

 

(2) 1/0-250 MCM

Summary of Contents for RTSN100J3S

Page 1: ...Automatic Transfer Switch Owner s Manual ATS Service Entrance HS Type Transfer Switch This manual should remain with the unit...

Page 2: ...e isolated from the NORMAL UTILITY power source by means of an approved transfer switch Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death t...

Page 3: ...while standing on metal or concrete place insulative mats over a dry wood platform Work on this equipment only while standing on such insulative mats Never work on this equipment while physically or...

Page 4: ...generator the generator then supplies the loads When UTILITY returns above a preset level the load is transferred back to the UTILITY and the generator shuts down 1 3 TRANSFER SWITCH DATA LABEL A DAT...

Page 5: ...he electrical loads that are to be connected to it Mount the switch vertically to a rigid supporting structure To prevent switch distortion level all mounting points If necessary use washers behind mo...

Page 6: ...Connect customer LOAD leads to switch termi nals T1 T2 T3 4 Connect neutral conductors of UTILITY EMERGENCY and customer LOAD to the neutral block Conductors must be properly supported of approved ins...

Page 7: ...perating the transfer switch manually or the manual handle could be damaged 3 2 1 CLOSE TO NORMAL SOURCE SIDE Before proceeding verify the position of the switch by observing window A in Figure 3 1 If...

Page 8: ...operate properly check that all three voltages are present and are of the correct voltage level DANGER FAILURE TO TURN OFF THE UTILITY SUPPLY BEFORE WORKING ON THE UTILITY CONNEC TIONS OF THE ATS WILL...

Page 9: ...frequency is correct but voltage is not the voltage regulator may require adjustment 3 4 GENERATOR TESTS UNDER LOAD 1 Set the generator s main circuit breaker to its OFF or OPEN position 2 Manually a...

Page 10: ...1 TRIPLE EKO SUITABLE FOR 1 1 25 1 50 CONDUIT 3 PLACES 179 5mm 7 1 490mm 19 3 61 5mm 2 4 41 5mm 1 6 MOUNTING HOLES 6 35mm 0 25 4 PLACES 430mm 16 9 Section 4 Installation Diagram RTS HS Type Transfer...

Page 11: ...1 TRIPLE EKO SUITABLE FOR 1 1 25 1 50 CONDUIT 3 PLACES 254mm 10 0 794mm 31 3 60 8mm 2 4 61 3mm 2 4 487mm 19 2 MOUNTING HOLES 6 35mm 0 25 4 PLACES Section 4 Installation Diagram RTS HS Type Transfer S...

Page 12: ...gram RTS HS Type Transfer Switch Drawing No 0F6405 TRIPLE EKO SUITABLE FOR 1 1 25 1 50 CONDUIT 3 PLACES 1220 9mm 48 1 332mm 13 1 1092mm 43 0 63 5mm 2 5 765 8mm 30 1 65 39mm 2 6 MOUNTING HOLES 6 35mm 0...

Page 13: ...4 S 600MCM A7822 S DISTRIBUTION PANEL 194 CUSTOMER CONNECTIONS WIRE 240 VAC 240 VAC WIRE N1 N2 N1 N2 NOTE WIRE ORIENTATION WARNING WIRE WIRE 23 23 194 057329 T CUSTOMER LOAD NEUTRAL BLOCK GROUND RTS T...

Page 14: ...TUATING COIL LS1 LS2 LS3 LIMIT SWITCHES ACTUATOR PM POWER MONITOR 3 PHASE UTILITY TR RELAY TRANSFER TS TERMINAL STRIP CUSTOMER CONNECTION 3 4 5 N2A N3 PM N1B PM F2 N2 N1 F1 N2B 126 F1 F2 FUSE 5A SENSI...

Page 15: ...H1 H4 X1 X4 H1 UTILITY 1 UTILITY 2 1 TB 2 3 4 23 194 5 Z Y NB N2B 205 E2A 126 N2B N3 N2A N1A E1A N1A N2A E2A E2 E1 N3 N3 194 E1A 23 205 N2 N1 23 194 E1 E2 N2A N1A N1A N2A N1A N2A E2A N3 N1C N1C N1C N2...

Page 16: ...UATING COIL GTS TRANSFER SWITCH CONTACTOR LS1 LS2 LS3 LIMIT SWITCHES ACTUATOR PM POWER MONITOR 3 PHASE UTILITY TR RELAY TRANSFER TS TERMINAL STRIP CUSTOMER CONNECTION 3 4 5 N1B N2A N3 PM N1B N1A PM F2...

Page 17: ...T1 T2 N1B N2A N3 E3 T3 2 1 8 7 3 4 5 6 126 205 N2A N2A N2A N1B N1B N1B N1B N1A N3 PM N3 N3 N1B N1B F2 F1 23 194 TS UTILITY 2 UTILITY 1 N2A N2A N2A N3 N3 N3 194 23 23 194 23 194 N1 N2 N2A N2A N2A N2A S...

Page 18: ...16 Section 6 Exploded Views and Parts List RTS HS Type Transfer Switch 100A Transfer Switch Assembly Drawing No 0G7277 C...

Page 19: ...TERMINAL SHOCK HAZARD 20 0C2262 1 DECAL TERMINAL STRIP 21 0F6165 2 WASHER M6 NYLON 3 22 0G5985L 1 DECAL XFRSW NON 100A 120 240 0G5968G 1 DECAL XFER SW NON 100A 120 240 23 064101 4 NUT HEX FL WHIZ 3 8...

Page 20: ...18 Section 6 Exploded Views and Parts List RTS HS Type Transfer Switch 200A Transfer Switch Assembly 120 280V Drawing No 0G2986 D...

Page 21: ...17 0A1661 2 RIVET POP 156 X 675 AL 18 0C4449A 1 ASS Y NTRL BL150 200A 19 0E2865 1 WELDMENT TRANSFER SWITCH BOX 20 0D3718 1 COVER TRANSFER SWITCH BOX 21 0G3259 2 DECAL TERMINAL SHOCK HAZARD BI 22 0C22...

Page 22: ...20 Section 6 Exploded Views and Parts List RTS HS Type Transfer Switch 200A Transfer Switch Assembly 277 480V Drawing No 0G2987 E...

Page 23: ...4 0F59510ST14 1 SUBPLATE 3R 200A XFER SW 08GRY 25 087680 1 NUT WING M6 1 0 26 063378 8 HOLDER CABLE TIE 27 064761 8 TIE WRAP UL 5 6 X 10 NATL 28 063321 1 HANDLE XFER SWITCH 1 400A 29 073590A 2 FUSE 5A...

Page 24: ...22 Section 6 Exploded Views and Parts List RTS HS Type Transfer Switch 100A Transfer Switch Assembly 120 280V Drawing No 0G2984 D...

Page 25: ...ITCH BOX 19 0C8308 2 DECAL TERMINAL SHOCK HAZARD 20 0C2262 1 DECAL TERMINAL STRIP 21 0F6165 2 WASHER M6 NYLON 22 PER MODEL 1 DECAL DATA XFER SW 23 064101 4 NUT HEX FL WHIZ 3 8 16 24 0E2866 1 SUBPLATE...

Page 26: ...24 Section 6 Exploded Views and Parts List RTS HS Type Transfer Switch 100A Transfer Switch Assembly 277 480V Drawing No 0G2985 E...

Page 27: ...DATA XFER SW 23 064101 6 NUT HEX FL WHIZ 3 8 16 24 0F59400ST14 1 SUBPLATE 24 36 ENCL RTS 08GRAY 25 087680 1 NUT WING M6 1 0 26 063378 8 HOLDER CABLE TIE 27 064761 8 TIE WRAP UL 5 6 X 10 NATL 28 063321...

Page 28: ...22 Select the prompt that describes the brand name of the generator THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED SPECIFICALLY GENERAC MAKES NO OTHER WARRANTIES AS TO THE MERC...

Reviews: