Generac Power Systems R-200 Technical Manual Download Page 7

 

 

5

GENERATOR OPERATION

The R-200 controller monitors the front panel switch 
position and reads the DIP switch position settings 
when the control board is initially powered-up.

In the OFF position the controller will only be incre-
menting the exercise timer and monitoring the bat-
tery voltage and low fuel pressure sensor.

In the MANUAL position the controller will start and 
run the generator. 

In the AUTO position the controller will go into a 
"standby" mode, where the controller will monitor 
the utility voltage and the exercise timer, and deter-
mine if the generator needs to be started and the load 
transferred. 

Battery voltage is continuously monitored and a 
warning LED is lit if the battery voltage drops below 
approximately 12.2 volts for longer than one (1) min-
ute. The LED will turn off when the battery voltage 
goes back above approximately 12.5 volts.

If, however, the battery voltage drops below 6V during 
cranking the low battery LED will stay lit.

While starting and running the engine, the controller 
will monitor the engine condition and shut the engine 
down on;

Over Crank
Over Speed
High Coolant Temperature
Low Coolant Level
Low Oil Pressure
Engine Speed Signal Loss/RPM Sensor Loss (the 

overspeed LED flashes to indicate this fault)

Dead Battery (battery voltage < 6V during crank-

ing)

ENGINE TIMING

Nominal engine timing when Natural Gas (NG) fuel 
is selected is: 

2.4L, 3600rpm engine is 32 degrees BTDC
3.0L, 3600rpm engine is 30 degrees BTDC

Nominal engine timing when LP fuel is selected is: 

2.4L, 3600rpm engine is 23 degrees BTDC
3.0L, 3600rpm engine is 23 degrees BTDC








UTILITY FAILURE

When the utility fails, a 15 second timer will start. 
If the utility is still gone when the timer expires the 
engine will crank and start. Once started a 10 sec-
ond engine warm-up timer will be initiated. When 
the warm-up timer expires, the R-200 controller will 
transfer the load to the generator (ATS Mode). The 
transfer of load when the generator is running is 
dependent upon the operating conditions as follows:

MANUAL MODE

The unit will not transfer if the utility is present, 
will un-transfer if the utility voltage is above 80% of 
nominal for > 15 seconds and will re-transfer if the 
utility voltage drops below 60% of nominal for >15 
seconds.

AUTO MODE

The engine will run if the utility fails for >15 sec-
onds, will not transfer if the utility is present, will 
un-transfer if the utility is above 80% of nominal for 
>15 seconds, and will stop the engine after a one 1 
minute cool-down time.

EXERCISE MODE

The unit will not exercise if the generator is already 
running (in manual or auto mode). The generator 
will only transfer if the utility fails during the exer-
cise period for >15 seconds, and the switch is in the 
AUTO mode above.

UTILITY RESTORED

When the utility returns, a 15 second timer will start. 
At the completion of this time, if the utility supply has 
been above 80% of nominal voltage for the previous 
15 seconds, the control will transfer the load back to 
the utility. When the load is transferred a one (1) min-
ute cool down timer will start, after which the engine 
will be shutdown.

INITIAL CRANKING

The initial crank cycle will be a 15 second crank fol-
lowed by a seven (7) second rest. This will be followed 
by 5 additional cycles of seven (7) second cranks fol-
lowed by seven (7) second rests. If the engine still 
fails to start, the overcrank LED will be illuminated. 

Based on the above, the maximum number of engine 
crank events is six (6), which is approximately 90 
seconds, prior to illuminating the overcrank LED.

‹

‹

‹

General Information

R-panel Technical Manual

Summary of Contents for R-200

Page 1: ...TECHNICAL MANUAL This manual should remain with the unit R 200 Digital Controller A new standard of reliability ...

Page 2: ...s and barri ers are in place before operating the equipment If working around an operating unit stand on an insulated dry surface to reduce potential shock hazards Do not handle any kind of electrical device while standing in water while barefoot or while hands or feet are wet DANGEROUS ELECTRICAL SHOCK MAY RESULT If people must stand on metal or concrete while installing operating servicing adjus...

Page 3: ...ed High Coolant Temp LED Indicator 7 Overspeed Red LED Indicator 7 RPM Signal Failure Flashing Red Overspeed Indicator 8 RPM Signal Failure During Cranking 8 RPM Signal Failure During Running 8 Overcrank Red LED Indicator 8 Invalid Cylinder Dip Switch Setting All Red LED s On 8 Alarm Cancel 8 Automatic Transfer Switch ATS Mode 8 Engineered Transfer Switch 2 wire Start GTS Mode 9 Voltage Regulator ...

Page 4: ...ing see Figure 1 To activate the DIP Switch settings place the AUTO OFF MANUAL switch in the OFF Mode make the DIP switch changes and then push and hold the Set Exercise Switch for five seconds DIP Switch Position 1 Reserved for future use The position of this DIP Switch does not affect generator operation DIP Switch Position 2 Selects the type of transfer switch to be used with the generator When...

Page 5: ...tart or not provide rated power When LP fuel is used it is very important that DIP Switch Position 4 be in the LP fuel position switch OFF LED Indicators visible through front panel see Table 1 and Figure 2 Table 1 System Ready Green LED Low Fuel Pressure Yellow LED Low Battery Red LED Low Oil Pressure Red LED Hi Coolant Temp Low Coolant Level Red LED Over Speed RPM Sensor Loss Red LED Over Crank ...

Page 6: ...down due OFF X ON O O To Low Oil Pressure Unit Shutdown due OFF X ON O O To High Cooant Temp Unit Shutdown due OFF X ON O O To Engine Overspeed Unit Failed to Start OFF X ON O O During it s Crank Cycle Utility Voltage is Flashing X O O 60 of Nominal 1 sec rate Unit Shutdown due OFF X Flashing O O To Low Coolant Level Engine Speed Signal OFF X Flashing O O Fault RPM Signal Loss Control Board is Fla...

Page 7: ...gone when the timer expires the engine will crank and start Once started a 10 sec ond engine warm up timer will be initiated When the warm up timer expires the R 200 controller will transfer the load to the generator ATS Mode The transfer of load when the generator is running is dependent upon the operating conditions as follows MANUAL MODE The unit will not transfer if the utility is present will...

Page 8: ... will stop flashing the indi vidual fault LED will turn on and the engine will be shut down Once the AUTO OFF MANUAL switch is switched to OFF the individual fault LED will turn off and the five 5 red LED s will begin flashing to show that the exercise mode has not yet been set LOW SPEED EXERCISE To select this mode place DIP switch position 3 in the OFF position In Low Speed Exercise mode the 2 4...

Page 9: ... visual LED warning only and does not trigger the controller alarm output Low fuel pressure sensing is active in all generator operat ing modes i e MANUAL OFF and AUTO LOW BATTERY RED LED INDICATOR The R 200 controller continually monitors the bat tery voltage and turns on the low battery LED if the battery voltage falls below approximately 12 2VDC for one minute A low battery voltage is a non lat...

Page 10: ...front panel will be ON all the time if DIP switch position 5 and DIP switch position 6 are not set correctly ALARM CANCEL When the generator is shut down on a latched fault or latching alarm the AUTO OFF MANUAL switch must be set to the OFF position to turn off the correspond ing fault LED Prior to moving the switch to the OFF position record which LEDs are ON or FLASHING and the date on the back ...

Page 11: ... NOT monitor the utility The generator control board will NOT perform a weekly exercise In GTS mode the green system ready LED will be ON for five 5 seconds and OFF for one 1 second The generator control board will NOT activate the transfer output The generator control board WILL monitor all engine conditions and shut down on all the faults listed in this document For the W Type transfer switch to...

Page 12: ...tch is in the manual posi tion AUTO The control board will monitor the 2 wire start circuit When the 2 wire start wire 178 is con nected to 2 wire start wire 183 via a relay contact closure in the W type transfer switch the control board will start and run the generator When the 2 wire start wire connection is opened the control board will stop the generator When the control board is in AUTO MANUA...

Page 13: ...act in W type transfer switch 5 Momentary Open Switch Input B 6 2 wire Start Return from relay contact in W type transfer switch 7 Manual Auto Input BS 8 19 5VAC Utility Sense Input 9 Alarm Relay Driver Output minimum coil resistance is 90 ohms 10 Transfer Relay Driver Output minimum coil resistance is 60 ohms 11 Manual Input 12 19 5VAC Utility Sense Return 13 Reserved Do not connect any wires to ...

Page 14: ...on Such an explosion can shat ter the battery and cause blindness or other injury Any area that houses a storage battery must be properly ventilated Do not allow smok ing open flame sparks or any spark producing tools or equipment near the battery Battery electrolyte fluid is an extremely corro sive sulfuric acid solution that can cause severe burns Do not permit fluid to contact eyes skin clothin...

Page 15: ... Undervoltage Shutdown typ 11 Volts LED Indicators AC Line Voltage 108Vac Green LED ON Battery Connected Charging Yellow LED ON the Green LED must be ON to obtain a valid battery charging indication Yellow LED ON if charge current approx 2 Amps Battery Current Drain AC Power OFF 30mA typ AC Line Connections via terminal block AC Hot AC Neut GND Battery Connections via terminal block Pos Neg Contro...

Page 16: ...Part No 0F9784 GENERAC POWER SYSTEMS INC P O BOX 8 WAUKESHA WI 53187 Revision B 06 07 06 Printed in U S A ...

Reviews: