background image

INTERCONNECTIONS

NEXUS™ CONTROL FEATURES

2-Line Plain Text LCD Display

Simple user interface for ease of operation

Mode Switch

-Auto 

Automatic Start on Utility failure. 7 day exerciser

-Off

Stops unit. Power is removed. Control and charger still operate.

-Manual/Test (start)

Start with starter control, unit stays on. If utility fails, transfer to load takes place.

Programmable start delay between 10-30 seconds

Standard

Engine Start Sequence

Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration)

Engine Warm-up

5 seconds

Engine Cool-Down

1 minute

Starter Lock-out

Starter cannot re-engage until 5 sec. after engine has stopped.

Smart Battery Charger

Standard

Automatic Voltage Regulation with Over and Under Voltage Protection

Standard

Automatic Low Oil Pressure Shutdown

Standard

Overspeed Shutdown

Standard, 72Hz

High Temperature Shutdown

Standard

Overcrank Protection

Standard

Safety Fused

Standard

Failure to Transfer Protection

Standard

Low Battery Protection

Standard

50 Event Run Log

Standard

Future Set Capable Exerciser

Standard

Incorrect Wiring Protection

Standard

Internal Fault Protection

Standard

Common External Fault Capability

Standard

Governor Failure Protection

Standard

QT036

CUSTOMER SUPPLIED

NEUTRAL WIRE

LIQUID-COOLED INSTALLATION

NEUTRAL BLOCK

UTILITY SUPPLY FROM

SERVICE DISCONNECT

TO BE RUN IN TWO DIFFERENT CONDUITS.

POWER LEADS AND TRANSFER SWITCH LEADS

NOTE:

N1

N1

CONNECTION PANEL

QT SERIES ENGINE GENERATOR

23

194

TERMINAL NUMBERS

NUMBERS TO 

MATCH WIRE

NOTE:

23

194

178

183

T1/LINE

ON

0

NEUT

T1

N2

E1

N2

NEU

E2

GROUND

0C4449A-T

(DISTRIBUTION PANEL)

CUSTOMER LOAD

NEUTRAL BLOCK

RTS TRANSFER SWITCH

UTILITY

STANDBY

(C1 & VR1)

(C2 & VR2)

0 GROUND

15B +12V

23 TRANSFER

AIR 1

AIR 2

PRIORITY 1

PRIORITY 2

PRIORITY 3

PRIORITY 4

T1

NEUTRAL

CONTACTOR

1

CONTACTOR

2

CONTACTOR

3

CONTACTOR

4

NOTE WIRE ORIENTATION

WARNING

TRANSFER

DC COMMON

CUST

OMER CONNECTIONS

23

0

194

+12VDC

GROUND

LOAD SHED

MODULE

194

23

0

T1

N1 N2

48850-T

E1

T1

E2 T2

T1

E1

N1

T2

E2

N2

N1

N2

*Single and three phase connections may vary, refer to the owner’s manual for specific connection information. 

Summary of Contents for Quitesource QT036

Page 1: ... surge loads to the engine An unequalled 1 voltage regulation SINGLE SOURCE SERVICE RESPONSE from Generac s extensive dealer network provides parts and service know how for the entire unit from the engine to the smallest electronic component GENERAC TRANSFER SWITCHES Long life and reliability are synonymous with GENERAC POWER SYSTEMS One reason for this confidence is that the GENERAC product line ...

Page 2: ...s protection against mother nature Electrostatically applied textured epoxy paint for added durability Enclosed critical grade muffler Quiet critical grade muffler is mounted inside the unit to prevent injuries Small compact attractive Makes for an easy eye appealing installation SAE Sound attenuated enclosure ensures quiet operation ENGINE SPECIFICATIONS MAKE Generac MODEL Inline 4 CYLINDERS 4 DI...

Page 3: ...er 60 Hz cfm 106 SOUND EMISSIONS IN DBA Exercising at 7 meters Normal operation at 7 meters 58 64 EXHAUST Exhaust flow at rated output 60 Hz cfm Exhaust temp at muffler outlet F 300 1075 ENGINE PARAMETERS Rated synchronous RPM 60 Hz 1800 POWER ADJUSTMENT FOR AMBIENT CONDITIONS Temperature Deration 3 for every 10 C above C 1 65 for every 10 F above F Altitude Deration 1 for every 100 m above m 3 fo...

Page 4: ...Low Battery Protection Standard 50 Event Run Log Standard Future Set Capable Exerciser Standard Incorrect Wiring Protection Standard Internal Fault Protection Standard Common External Fault Capability Standard Governor Failure Protection Standard QT036 CUSTOMER SUPPLIED NEUTRAL WIRE LIQUID COOLED INSTALLATION NEUTRAL BLOCK UTILITY SUPPLY FROM SERVICE DISCONNECT TO BE RUN IN TWO DIFFERENT CONDUITS ...

Page 5: ...INSTALLATION LAYOUT QT036 ...

Page 6: ...704 Paint Kit Medium Grey Kit 5984 Scheduled Maintenance Kit The Liquid Cooled Scheduled Maintenance Kits offer all the hardware necessary to perform a complete maintenance on Generac liquidcooled generators 5928 Nexus Wireless Remote Completely wireless and battery powered Generac s Nexus wireless remote monitor provides you with instant status information without ever leaving the house 5951 Adva...