32
• Carefully prepare conduit ends to prevent sharp edges from
cutting through wiring insulation.
• Route conduit so it does not interfere with generator movement.
• If using metallic conduit, vapor-seal the end of the conduit
where it enters the junction box. Do this because flexible metal-
lic conduit is not vapor proof along its entire length.
• All openings in the generator compartment for the passage of
wiring and conduit must be sealed and made vapor-tight.
NOTE:
Use a high-quality silicone rubber base sealant or other
approved method (such as, explosion-proof fittings) to seal
such openings.
2.6.5 POWER SUPPLY CORD
The power supply cord must comply with all applicable codes,
standards, and regulations. It must be large enough to handle the
full amperage to which it will be subjected.
2.6.6 GROUND FAULT CIRCUIT INTERRUPTERS
The National Electrical Code (NFPA 70, 551-7) requires that
ground-fault circuit interrupters (GFCIs) be installed on all external
and some internal electrical receptacles. Contact the manufacturer
or dealer for recommendations.
2.6.7 ISOLATING DIFFERENT POWER SOURCES
Connections from the junction box must terminate in a double-
pole, double-throw transfer switch (Figure 2.17). An alternate
method for isolating different power sources includes using an
isolating receptacle (Figure 2.18). Whichever method is used, be
certain that both power sources are NOT connected at the same
time.
If the vehicle’s electrical circuits can be
powered by any other source of electricity
(such as, a “dockside” power receptacle),
there must be no possibility of connecting
the different power sources to the vehicle’s
circuits at the same time. The dockside (util-
ity) power source must be positively isolated
from the vehicle’s circuits whenever the gen-
erator is operating. Failure to isolate the vehi-
cle’s circuits from the dockside power supply
when the generator is running may result in
damage to the generator or in serious injury
or death to dockside (utility) power work-
ers due to backfeed of electrical energy.
Installation and connection of the generator
must comply with NFPA 70, Article 551, and
NFPA 1192 (latest editions).
Figure 2.17 – Transfer Switch Isolation Method
Installation
Summary of Contents for quietpact 85d
Page 23: ...21 Figure 1 2 Major Features and Dimensions Drawing 0G6806 A General Information ...
Page 40: ...38 Electrical Data Schematic 120 240 VAC Output Drawing No 0G7332 C ...
Page 41: ...39 Schematic 120 240 VAC Output Drawing No 0G7332 C Electrical Data ...
Page 42: ...40 Electrical Data Schematic 120 240 Dual Voltage Drawing No 0G7333 D ...
Page 43: ...41 Schematic 120 240 Dual Voltage Drawing No 0G7333 D Electrical Data ...
Page 44: ...42 Electrical Data Schematic 120 240 Dual Voltage Drawing No 0G7333 D ...
Page 45: ...43 Schematic 120 240 Dual Voltage Drawing No 0G7333 D Electrical Data ...
Page 46: ...44 Exploded Views Parts Lists Engine Alternator Starter Assy Drawing No 0G7350 B ...
Page 48: ...46 Exploded Views Parts Lists Enclosure Drawing No 0G7351 B ...
Page 50: ...48 Exploded Views Parts Lists Cooling System Drawing No 0G7352 B ...
Page 52: ...50 Exploded Views Parts Lists Fuel Electrical Systems Drawing No 0G7355 A ...
Page 54: ...52 Exploded Views Parts Lists Customer Controls Assy Drawing No 0G7356 B ...
Page 73: ......
Page 75: ......
Page 77: ......
Page 79: ......
Page 81: ......
Page 83: ......
Page 85: ......
Page 87: ......
Page 89: ......
Page 91: ......
Page 93: ......
Page 95: ......
Page 97: ......
Page 99: ......
Page 101: ......
Page 103: ......
Page 105: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......