background image

GENERATOR

 ...................................................................................................................................

Model 05418 - Aluminum

Rated Maximum Continuous Power Capacity (LP) ....................................................................................18,000 Watts*
Rated Maximum Continuous Power Capacity (NG) ...................................................................................16,000 Watts*
Rated Voltage ..................................................................................................................................................120/240
Rated Maximum Continuous Load Current
     240 Volts .............................................................................................................................................75.0 LP/66.6 NG
Main Line Circuit Breaker ................................................................................................................................80 Amp
Phase ................................................................................................................................................................... 1
Number of Rotor Poles ......................................................................................................................................... 2
Rated AC Frequency .........................................................................................................................................60Hz
Power Factor ........................................................................................................................................................ 1
Battery Requirement (not included)  .......................................................Group 26, 12 Volt Negative Ground and 525 Cold-cranking Amperes Minimum
Unit Weight .................................................................................................................................................. 451 Pounds
Dimensions (L” x W” x H”) .........................................................................................................................48 x 24 x 28-1/4 
Sound output in dB(A) at 23 ft. with generator at normal operating load ............................................................ 66
Sound output in dB(A) at 23 ft. with generator in Quiet-Test™ exercise mode .................................................. 60

ENGINE

 ............................................................................................................................................

Model 05418 - Aluminum

Type of Engine ...................................................................................................................................GENERAC OHVI V-TWIN
Number of Cylinders ............................................................................................................................................. 2 
Rated Horsepower.................................................................................................................................. 31.5 @ 3,600 rpm
Displacement .................................................................................................................................................... 992cc
Cylinder Block................................................................................................................................ Aluminum w/Cast Iron Sleeve
Valve Arrangement ................................................................................................................................... Overhead Valve
Ignition System .................................................................................................................................... Solid-state w/Magneto
Governor System........................................................................................................................................... Electronic
Compression Ratio ............................................................................................................................................ 9.5:1
Starter ...............................................................................................................................................................12Vdc
Oil Capacity Including Filter ..................................................................................................................... Approx. 1.7 Qts.
Standby Operating RPM ...................................................................................................................................3,600
Exercise RPM ....................................................................................................................................................2,400
Fuel Consumption
       Natural Gas    cu.ft./hr. 
                                           1/2 Load .............................................................................................................181.3
                                           Full Load ............................................................................................................. 262
       Liquid Propane     ft3/hr (gal/hr)
                                           1/2 Load ........................................................................................................ 71.6 (1.97)
                                           Full Load ...................................................................................................... 103.5 (2.85)

Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas 

CONTROLS

Mode Switch
 -Auto 

 

– 

Automatic start and stop on utility failure and return. 7 day exerciser.

 

 

 

 

Cyclic cranking 7 seconds on, 7 seconds rest for 90 seconds maximum.   

 

 

 -Off 

 

 

– 

Stops unit. Power is removed from controller.  

 

 

 

 

Battery charger will still operate. 

 -Manual/Test 

(start) 

 

– 

Start with starter control, unit will stay on.  If utility fails, transfer will take place.

Home Standby – 18kW

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage.  No overload capability is available for this rating.  (All ratings in accordance with BS5514, 
ISO3046 and DIN6271).  Prime (Unlimited Running Time): Unit not recommended for prime power applications.  Applicable for supplying electric power in lieu of commercially purchased power.  Prime power is 
the maximum power available at variable load.  A 10% overload capacity is available for 1 hour in 12 hours.  (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).* Maximum wattage and 
current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.  Maximum power decreases about 3.5 percent for each 1,000 feet above 
sea level; and also will decrease about 1 percent for each 12° C (10° F) above 15.5° C (60°F). 

Transfer Switch Rating ...........................100/200/400 Amps
Number of Poles................................................................. 2
UL Listed ........................................................ Yes, UL 1008
Enclosure.................................................................NEMA 1
.............................................................................. NEMA 3R
Interrupt Rating ................................................10,000 Amps
Maximum Switching Time.......................... 160 Milliseconds
Maximum Voltage .................................................. 240 Volts
Exercise Time .................Automatic 15 Minutes Each Week

HOME STANDBY TRANSFER SWITCH (ORDERED SEPARATELY)

Summary of Contents for QUIET TEST 5418

Page 1: ...ed FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque matching the surge loads to the engine SINGLE SOURCE SERVICE RESPONSE from Generac s dealer network provides parts and service know how for the entire unit from the engine to the smallest electronic component You are never on your own when you own a GENERAC POWER SYSTEM GENERAC TRANSFER SWIT...

Page 2: ... low oil Prevents damage due to overheating Allows for smaller light weight unit that operates 25 more efficiently than a revolving armature generator Maximizes motor starting capability Provides more surge capability than brushless generator designs Regulates the output voltage to 2 prevents damaging voltage spikes For your safety Transfers your vital electrical loads to the energized source of p...

Page 3: ...P gas CONTROLS Mode Switch Auto Automatic start and stop on utility failure and return 7 day exerciser Cyclic cranking 7 seconds on 7 seconds rest for 90 seconds maximum Off Stops unit Power is removed from controller Battery charger will still operate Manual Test start Start with starter control unit will stay on If utility fails transfer will take place Home Standby 18kW Rating definitions Stand...

Page 4: ...ff Solenoid Flexible Fuel Lines Secondary Fuel Regulator N G and L P Critical Exhaust Silencer Battery Charge Alternator Battery Trickle Charger Battery Cables Main Line Circuit Breaker Battery Tray Weather Protective Enclosure Locking Type HOME STANDBY CONTROL FEATURES Home Standby Control Console Manual Auto Off switch Fault indicator lamps Fuse panel overload Set exercise time switch Home Stand...

Reviews: