Fuel Conversion/Gas Connections
18
Installation Guidelines for 60 Hz PowerPact™
Fuel Consumption
Generator
Natural Gas
LP Vapor
1/2 Load
Full Load
1/2 Load
Full Load
6 / 7.5 kW
73 / 2.07
117 / 3.31
0.87 / 3.29 / 31.6
1.42 / 5.37 / 51.6
* Natural gas is in ft
3
/h / cm
3
/h
** LP is in gal/h / l/h / ft
3
/h
*** Values given are approximate. Use the appropriate spec sheet or Owner’s Manual for specific values.
Verify gas meter is capable of providing enough fuel flow to include household appliances and all other loads.
NOTE:
The gas supply and pipe MUST be sized at 100% load BTU / Megajoule rating.
Always refer to the Owner’s Manual for the proper BTU, Megajoule and required gas pressures:
•
Natural Gas:
BTU = ft
3
/h x 1000
Megajoules = m
3
/h x 37.26
•
Liquid Propane Vapor
BTU = ft
3
/h x 2500
Megajoules = m
3
/h / hour x 93.15