Generac
®
Power Systems, Inc.
13
Section 3 — Operation
PM-GC
Low Battery Voltage (1/100ths volt)
Warning
Alarm
Units
Comment
Setpoint
Shutdown
N
Dialout
N
Common alarm
Y
Alarm log
N
Sensor failure detection
N
Shutdown on sensor failure
N
Delay
60 seconds
seconds
Active
Hold off
Hysteresis
200
1/100ths volt
High Battery voltage (1/100ths volt)
Setpoint
Shutdown
N
Dialout
N
Common alarm
Y
Alarm log
N
Sensor failure detection
N
Shutdown on sensor failure
N
Delay
0
seconds
Active
Hold off
Hysteresis
200
1/100ths volt
High Gen. Voltage A,B,C (Volts RMS)
Setpoint
Shutdown
N
Dialout
N
Common alarm
Y
Alarm log
Y
Sensor failure detection
N
Shutdown on sensor failure
N
Delay
0.5 seconds
seconds
Active
Hold off
Hysteresis
10
Vrms
Low Gen. Voltage A,B,C (Volts RMS)
Setpoint
Shutdown
N
Dialout
N
Common alarm
Y
Alarm log
Y
Sensor failure detection
N
Shutdown on sensor failure
N
Delay
0.5 seconds
seconds
Active
Hold off
Hysteresis
10
Vrms
Over Speed (rpm)
Setpoint
Shutdown
Y
Dialout
Y
Common alarm
Y
Alarm log
Y
Sensor failure detection
Y
Shutdown on sensor failure
Y
Delay
0.1 seconds
seconds
Active
Immediate
Hysteresis
20
RPM