Generac Power Systems Nexus smart Technical Manual Download Page 6

 4 

Before connecting wiring cables to terminals, remove any surface 

oxides from the cable ends with a wire brush. All power cables 

should enter the switch next to transfer mechanism terminals. 

If ALUMINUM conductors are used, apply corrosion inhibitor to 

conductors. Tighten terminal lugs to the torque values as noted on 

the decal located on the inside of the door. After tightening terminal 

lugs, carefully wipe away any excess corrosion inhibitor.
All power cables should enter the switch next to the transfer 

mechanism terminals.

 

 

Use a torque wrench to tighten the conductors, 

being sure not to overtighten, or damage to the 

switch base could occur. If undertightened, a 

loose connection would result, causing excess 

heat which could damage the switch base.

Connect power source load conductors to clearly marked transfer 

mechanism terminal lugs as follows:
1.  Connect UTILITY (NORMAL) power source cables to switch 

terminals N1, N2.

2.  Connect EMERGENCY (STANDBY) source power cables to 

transfer switch terminals E1, E2.

3.  Connect customer LOAD leads to switch terminals T1, T2.
4.  Connect neutral conductors of UTILITY, EMERGENCY and 

customer LOAD to the neutral block.

Conductors must be properly supported, of approved insulative 

qualities, protected by approved conduit, and of the correct wire 

gauge size in accordance with applicable codes.
Be sure to maintain proper electrical clearance between live metal 

parts and grounded metal. Allow at least 1/2 inch for 100-400 

amp circuits.

2.4  

CONNECTING START CIRCUIT

WIRES

Control system interconnections consist of UTILITY 1 (N1), 2 (N2), 

Load (T1) and leads 23 and 194. Recommended wire gauge sizes 

for this wiring depends on the length of the wire, as recommended 

below:

MAXIMUM WIRE LENGTH

RECOMMENDED WIRE 

SIZE

460 feet (140m)

No. 18 AWG.

461 to 730 feet (223m)

No. 16 AWG.

731 to 1,160 feet (354m)

No. 14 AWG.

1,161 to 1,850 feet (565m)

No. 12 AWG.

2.5  

CONNECTING LOAD SHED 

MODULE (LSM) CONNECTIONS

The LSM can control an air conditioner (24 Vac) directly or a sepa-

rate contactor (120 Vac) which can control any load connected to 

it. See Figure 2.2.

2.5.1   SEQUENCE OF OPERATION

The 4 green status LEDs will indicate when a load priority level is 

enabled.
•  All loads are enabled when the transfer signal is off. (ATS in 

Utility position).

•  If the transfer signal is pulled low (Active)

•   All loads are enabled until an overload is detected
•   When an overload is detected all loads are disabled
•   After 5 minutes priority 1 loads are enabled.
•   After another 30 seconds priority 2 loads are enabled
•   After another 30 seconds priority 3 loads are enabled
•   After another 30 seconds priority 4 loads are enabled 

If an overload is detected within 30 seconds of a level being 

enabled, all loads are disabled again and the sequence repeats. 

However, the level that caused the overload and all levels higher 

will not be enabled again for 30 minutes.

Control of Air Conditioner Load

1.  Route the thermostat cable (from the furnace/thermostat to 

the outdoor air conditioner unit) to the transfer switch.

2.  Connect the wire to the terminal strip terminals (Air 1) on 

the LSM as shown in Figure 2.2. These are normally closed  

contacts which open upon load shed conditions. Route ther-

mostat wire away from High voltage wires.

3.  If required, connect the second air conditioner to the terminal 

strip terminals (Air 2).

Contact Ratings

Air 1 & 2

24 VAC, 5.0 Amps Max

NOTE:

These instructions are for a typical air conditioner installation. 

Control of heat pump and 2-stage air conditioners will require 

special connections.

Control of a Separate Contactor

A separate contactor relay module can be purchased from the 

manufacturer. If a different relay is used it must have a 120 Vac 

coil voltage. The LSM supplies fused (5A) 120 Vac to energize the 

coils of the relay contactors (contactor 1, 2, 3 or 4).
1.  Mount the contactor module and connect the load to the main 

contacts. 

2.  Connect the contactor coil to the desired LSM (contactor 1, 2, 

3 or 4) terminals on the terminal strip.

3.  Connect additional load shedding contactors in a similar fash-

ion.

Installation

Summary of Contents for Nexus smart

Page 1: ...This manual should remain with the unit Technical Manual Nexus Smart Switch...

Page 2: ...system from utility distribution system when the generator is operating Article 701 Legally Required Standby Systems or Article 702 Optional Standby Systems as applicable Failure to isolate electric s...

Page 3: ...and national electrical and building codes When using this equipment comply with regulations the National Electrical Code NEC CSA Standard C22 1 Canadian Electric Code and Occupational Safety and Heal...

Page 4: ...the event of a drop in generator frequency overload Loads to be shed are grouped in 4 priority levels on the LSM Priority 1 and 2 has connections for both one air conditioner and one contactor Both a...

Page 5: ...mensions drawing Handle transfer switches carefully when install ing Do not drop the switch Protect the switch against impact at all times and against con struction grit and metal chips Never install...

Page 6: ...IONS The LSM can control an air conditioner 24 Vac directly or a sepa rate contactor 120 Vac which can control any load connected to it See Figure 2 2 2 5 1 SEQUENCE OF OPERATION The 4 green status LE...

Page 7: ...ormally Open Open Closed Common to Normally Closed Closed Open NOTE Auxiliary Contacts are rated 10 amps at 125 or 250 volts AC DO NOT EXCEED THE RATED VOLTAGE AND CURRENT OF THE CONTACTS Figure 2 3 4...

Page 8: ...SOURCE SIDE Before proceeding verify the position of the switch by observing window A in Figure 3 1 on page 6 If window A reads ON the contacts are closed in the normal position no further action is r...

Page 9: ...2 to NEUTRAL 120 123 VAC Failure to do so may result in damage to cer tain rotary equipment 5 When certain that UTILITY supply voltage is correct and compatible with transfer switch ratings turn OFF t...

Page 10: ...etting the AUTO OFF MANUAL switch to its OFF position 7 Move the switch s main contacts back to the UTILITY position For example load connected to utility power supply Refer to Manual Operation Handle...

Page 11: ...9 Interconnection Drawing No 0H7453 C Electrical Data...

Page 12: ...10 Electrical Data Wiring Diagram Schematic Drawing No 0H7257 C...

Page 13: ...11 Wiring Diagram Schematic Drawing No 0H7257 C Electrical Data...

Page 14: ...12 Parts List on page 14 Exploded Views Parts Lists 400A Assembly Drawing No 0H7267 C...

Page 15: ...13 Parts List on page 14 400A Assembly Drawing No 0H7267 C Exploded Views Parts Lists...

Page 16: ...J3806C 1 DECAL DATA XFER SW 23 064101 6 NUT HEX FL WHIZ 3 8 16 24 0F59400ST14 1 SUBPLATE 24 36 ENCL RTS GY4 25 087680 1 NUT WING M6 1 0 26 063378 4 HOLDER CABLE TIE 27 064761 4 TIE WRAP UL 5 6 X 10 NA...

Page 17: ...9 6mm 24 0 917mm 36 1 TRIPLE EKO SUITABLE FOR 1 1 25 1 50 CONDUIT 3 PLACES 254mm 10 0 794mm 31 3 60 8mm 2 4 61 3mm 2 4 487mm 19 2 MOUNTING HOLES 6 35mm 0 25 4 PLACES Installation Diagram Drawing No 0F...

Page 18: ...16 Notes...

Page 19: ...17 Notes...

Page 20: ...Part No 0H7443 Revision C 08 05 11 Printed in U S A...

Page 21: ......

Page 22: ...AL DATA XFERSW 0J3806C 1 DECAL DATA XFERSW 23 064101 6 NUT HEX FL WHIZ 3 8 16 24 0F59400ST14 1 SUBPLATE 24 36 ENCL RTS GY4 25 087680 1 NUT WING M6 1 0 26 063378 4 HOLDER CABLE TIE 27 064761 4 TIE WRAP...

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ......

Reviews: