21
30 seconds to allow the starter motor to cool and then repeat the starting procedure.
Excessive cranking will cause damage to the starter.
Note: If oil pressure is not obtained within 15 seconds after the key is switched to the “RUN” position, the low oil
automatic shutdown will turn off the fuel supply, stopping the engine. Check the oil level and turn the key to the “OFF”
position to reset the oil pressure timer before attempting to restart the engine.
3.
Once the engine is running, allow it to reach normal operating temperature before switching on any loads.
AUTOMATIC SHUTDOWN
This unit is equipped with a low oil pressure and high coolant temperature automatic shutdown system. This system
will automatically shut off the fuel supply to stop the engine if oil pressure drops too low or the engine exceeds normal
operating temperature. Return the Control Power switch to the OFF (O) position to reset the unit after you have
determined the cause of the shutdown.
LIGHT OPERATION
WARNING
NEVER OPERATE THE LIGHTS WITHOUT THE PROTECTIVE LENS COVER, OR WITH
A LENS COVER THAT IS CRACKED OR DAMAGED. The bulbs in the light fixtures
produce high temperatures and operate under pressure. A broken or missing lens
cover could cause the bulbs to shatter, causing injury.
1.
Once the engine is up to temperature and running
smoothly, switch the main circuit breaker (A) to the
ON (I) position.
2.
With the main circuit breaker on, switch each individ-
ual circuit breaker for the lights (B) to ON (I), one at
a time.
3.
The ballast indicator lights (C) will come on and
continue to get brighter as the lights warm up, and
then remain on. This confirms that power is coming
from the ballasts to the lights.
4.
If an indicator light does not come on, the ballast may
need to be serviced. If the indicator light comes on
and stays lit, but the related light is not illuminated,
check the bulb or the mast wiring. Refer to
shooting the Lights” on page 31.
5.
The lights require a warm up period of 5-15 minutes before they reach full output. If the lights are shut down,
they require a cool down period of approximately 10 minutes before they can be switched on again.
6.
The light tower uses four 1000W bulbs. When checking or replacing the bulbs, wipe them with a clean cloth to
avoid leaving any grease, oil residue or fingerprints on the glass. Any residue can create a hot spot on the bulb,
causing premature bulb failure.
CAUTION
Bulbs become extremely hot when in use. Allow bulb fixture to cool 10-15 minutes before
handling or lowering the mast.
NEUTRAL BONDED TO FRAME
BALLAST INDICATOR LIGHTS
MAST LIGHT SWITCHES
I
O
I
O
I
O
I
O
GLOW PLUG
INDICATOR
OFF
RUN
START
GLOW
PLUGS
TURN
MAIN
BREAKER
OFF
240VAC
MAIN CIRCUIT
BREAKER
ON
ON
ON
ON
ON
ON
A
B
C