
Owner’s Manual for Portable Generator
9
Adequate, unobstructed flow of cooling and
ventilating air is critical to correct generator
operation. Do not alter the installation or per-
mit even partial blockage of ventilation provi-
sions, as this can seriously affect safe
operation of the generator. The generator
MUST be operated outdoors.
This exhaust system must be properly main-
tained. Do nothing that might render the
exhaust system unsafe or in noncompliance
with any local codes and/or standards.
Always use a battery operated carbon monox-
ide alarm indoors, installed according to the
manufacturer's instructions.
3.3.1 — Grounding The Generator If Used
As A Portable
This generator has an equipment ground that connects
the generator frame components to the ground terminals
on the AC output receptacles (see NEC 250.34 (A) for
explanation). This allows the generator to be used as a
portable without grounding the frame of the generator as
specified in NEC 250.34.
Figure 3-6. Grounding the Generator
3.3.1.1 — Special Requirements
There may be Federal or State Occupational Safety and
Health Administration (OSHA) regulations, local codes,
or ordinances that apply to the intended use of the gener-
ator.
Please consult a qualified electrician, electrical inspector,
or the local agency having jurisdiction:
• In some areas, generators are required to be regis-
tered with local utility companies.
• If the generator is used at a construction site, there
may be additional regulations which must be
observed.
3.3.2 — Connecting To A Building’s
Electrical System
When connecting directly to a building’s electrical sys-
tem, it is recommended that a manual transfer switch is
used. Connections for a portable generator to a building’s
electrical system must be made by a qualified electrician
and in strict compliance with all national and local electri-
cal codes and laws.
3.4 — Do Not Overload Generator
Overloading a generator in excess of its rated wattage
capacity can result in damage to the generator and to
connected electrical devices. Observe the following rules
to avoid overloading:
• Add up the total wattage of all electrical devices to
be connected at one time. The total should NOT be
greater than the wattage capacity of the generator.
• The rated wattage of lights can be taken from light
bulbs. The rated wattage of tools, appliances and
motors can usually be found on a data label or
decal affixed to the device.
(000103)
DANGER
Asphyxiation. Running engines produce carbon
monoxide, a colorless, odorless, poisonous gas.
Carbon monoxide, if not avoided,
will result in death or serious injury.
*
*
*