Installation
Automatic Transfer Switch Owner’s Manual
15
Install Transfer Switch and SACM Kit
(RBU Only)
1.
See
. Remove screws (A) from bus bar
assembly and set aside.
2.
Remove screws (B) from bus bar assembly and
remove assembly from sub panel.
Figure 3-8. Remove Bus Bar Assembly
3.
See
. Use provided M5 screws (C) to
install transfer switch assembly from kit G0074000.
4.
Install screws (A) from step 1 and tighten to 72
in-
lbs
onto circuit breaker.
5.
Install SACM unit from kit G074000 into bracket
provided (D).
6.
Plug harness with 8 pin connector into SACM unit
(D).
7.
Follow RXUW instructions to connect SACM to
genset.
Figure 3-9. Install Kit G0074000
A
B
010495
A
C
D
010496
Summary of Contents for G0074000
Page 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank ...
Page 8: ...Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank ...
Page 20: ...Installation 16 Automatic Transfer Switch Owner s Manual This page intentionally left blank ...
Page 31: ......