General Information
Automatic Transfer Switch Owner’s Manual
7
See
. The SACM has a test button (C) used to
simulate an overload condition. This button operates
even when the transfer signal is inactive. The Generator
Control Wiring is connected to terminals (D).
Figure 2-2. Smart A/C Module (SACM)
Application Considerations
Generator overload condition is determined by generator
frequency. Loads are shed when frequency is less than
58 Hz for three seconds or less than 50 Hz for ½ second
(for 60 Hz systems).
The SACM can be used in conjunction with individual
SMMs to manage a combined total of eight loads.
•
Use Priorities A/C 1-4 on the SACM as the top
priorities, then up to four SMMs as Priorities 5-8.
•
Use only select A/C priorities on the SACM as the top
priorities, then use additional SMMs as the remaining
priorities.
•
A SMM can share a priority with an A/C priority on
the SACM provided the generator is sized to handle
the combined surge load from both appliances.
Sharing priorities can allow up to 12 loads to be
managed in a properly sized system.
In any combination of modules, the recovery times after a
loss of utility power or shutdown due to overload are
shown in
.
See the SMM Owner’s/Installation Manual for detailed
characteristics and specifications of that product.
T1
1
1
1
1
2
2
2
2
T1
N1
N2
0 DC GROUND
194 +12 VDC
N1
N2
T1
23 TRANSFER
®
®
A
B
C
D
006783
Table 1. Priority Settings
Priority
Recovery Time
SACM
SSMM
1
5 minutes
Yes
Yes
2
5 minutes 15 seconds
Yes
Yes
3
5 minutes 30 seconds
Yes
Yes
4
5 minutes 45 seconds
Yes
Yes
5
6 minutes
NA
Yes
6
6 minutes 15 seconds
NA
Yes
7
6 minutes 30 seconds
NA
Yes
8
6 minutes 45 seconds
NA
Yes
Summary of Contents for G0074000
Page 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank ...
Page 8: ...Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank ...
Page 20: ...Installation 16 Automatic Transfer Switch Owner s Manual This page intentionally left blank ...
Page 31: ......