General Information
Owner’s Manual for 50 Hz Air-Cooled Generator Sets
15
Fuel Requirements
The engine has been fitted with a dual fuel carburetion
system. The unit will run on NG or LP gas (vapor), but it
has been factory set to run on NG. The fuel system will
be configured for the available fuel source during installa-
tion.
Recommended fuels should have a MJ/BTU content of at
least 37.26 megajoules per cubic meter (1,000 BTUs per
cubic foot) for NG, or at least 93.15 megajoules per cubic
meter (2500 BTUs per cubic foot) for LP gas (vapor).
NOTE:
If converting to LP gas from NG, a minimum LP
tank size of 946 L (250 gal) is recommended. See instal-
lation manual for complete procedures and details.
Battery Requirements
12 volts, Group 26R-540CCA minimum or Group
35AGM-650CCA minimum (not included with unit.) See
for correct battery maintenance proce-
dures.
Battery Charger
The battery charger is integrated into the control panel
module in all models. It operates as a smart charger,
ensuring output charging levels are safe and continu-
ously optimized to promote maximum battery life.
NOTE:
A warning is displayed on the LCD when battery
needs service.
NOTE:
Do not use external battery chargers.
Engine Oil Requirements
See
for correct oil viscosity.
Activating the Generator Set
The generator set should be activated upon initial start-
up. See installation manual for complete instructions.
Wi-Fi Module
The generator set is equipped with a Wi-Fi module. See
Wi-Fi module user manual for further instructions.