Generac Power Systems G0071020 Instruction Sheet Download Page 3

Figure 7. Routing Heater Wires (11-22kW)

5.

See 

Figure 8

. Pass the lead wires through the customer

connection panel grommet (D). If the empty Y-harness
socket (E) will not be connected to a battery heater, coil the
wires and secure with a plastic wire tie. Secure all wires with
plastic wire ties at least 0.5 in. (1 cm) away from fuel hoses. 

Figure 8. Lead Wires to Customer Connection (11-22kW)

6.

Proceed to 

Connecting Lead Wires

.

Connecting Lead Wires

2016 and Newer Units—

See 

Figure 9

Connect the lead wires to the 240 VAC Input

Sense terminals N1 and N2 as shown.

Figure 9.  Input Sense Terminal Block

NOTE: 

It does not matter which lead wire goes into N1 or N2.

2013-2015 Units—

See 

Figure 10

Connect the lead wires to the 240 VAC Input

Sense terminals N1 and N2 as shown.

Figure 10.  Input Sense Terminal Block

NOTE: 

It does not matter which wire goes into N1 or N2.

Completing Installation

1.

Verify all wire routings are clear of pinch points and other
damage. Use tie wraps where necessary.

2.

Install customer connection panel cover.

3.

Return the utility power supply to the transfer switch:
• For service rated transfer switches, turn the main breaker ON.
• For non-service-rated switches, turn power feeder breaker ON.

4.

If removed, install the T1, N1 and N2 fuses in the transfer
switch.

5.

Install controller fascia (2013–2015 units) or intake side
panel (2016 and newer units), front panel, and 7.5A DC
fuse.

6.

Complete the installation wizard programming.

7.

Move the main line circuit breaker (generator disconnect)
to ON (closed).

8.

Place the generator controller in AUTO and close lid.

002826

C

002780

D

E

002781

002887

(000135)

CAUTION

Engine damage. Verify proper type and quantity of 
engine oil prior to starting engine. Failure to do so 
could result in engine damage.

Part No. 10000003502      Rev B   07/14/17
©2017 Generac Power Systems, Inc.
All rights reserved
Specifications are subject to change without notice.
No reproduction allowed in any form without prior written consent from 
Generac Power Systems, Inc.

Generac Power Systems, Inc.

S45 W29290 Hwy. 59

Waukesha, WI 53189

1-888-GENERAC (1-888-436-3722)

www.generac.com

Summary of Contents for G0071020

Page 1: ...r instead of turning off the normal power circuit breaker 4 With the generator shut down remove controller fascia 2013 2015 units or intake side panel 2016 and newer units front panel and 7 5A DC fuse...

Page 2: ...grommet D If the empty Y harness socket E will not be connected to a battery heater coil the wires and secure with a plastic wire tie Secure all wires with plastic wire ties at least 0 5 in 1 cm away...

Page 3: ...mage Use tie wraps where necessary 2 Install customer connection panel cover 3 Return the utility power supply to the transfer switch For service rated transfer switches turn the main breaker ON For n...

Page 4: ...star en OFF el disyuntor de alimentaci n normal 4 Con el generador apagado quite la fascia del controlador unidades fabricadas entre 2013 y 2015 o el panel de entrada de aire lateral unidades fabricad...

Page 5: ...e D Si el z calo vac o del arn s en Y E no se conectar a un calentador de bater a enrolle los cables y f jelos con un amarre de cables de pl stico Fije todos los cables con amarres de cables de pl sti...

Page 6: ...2 Instale la cubierta del panel de conexiones del cliente 3 Devuelva el suministro de alimentaci n del servicio p blico al interruptor de transferencia En los interruptores de transferencia para acome...

Page 7: ...s le g n rateur l arr t d posez la b che de protection du contr leur sur les appareils fabriqu s entre 2013 et 2015 ou le panneau lat ral d admission sur les appareils fabriqu s depuis 2016 le panneau...

Page 8: ...nts du client D Si aucun chauffe batterie ne sera branch sur la prise non utilis e du faisceau de fils en Y E roulez les fils et fixez les l aide d un fil d attache en plastique Fixez tous les fils av...

Page 9: ...t en place 3 R tablissez l alimentation du r seau public au commutateur de transfert Si vous utilisez des commutateurs de transfert automatiques cot s pour entr e de service placez le disjoncteur prin...

Page 10: ...1 G0071020 HSB 2013 240 N1 N2 Y 5W 30 25 1 2 OFF 3 T1 N1 N2 4 2013 2015 2016 7 5 A 5 OFF 6 7 5 7 1 2 A 1 2016 000100a 000182a 000139 000210 000236 002917...

Page 11: ...2 2 2013 2015 9 1 2 3 3 9 3 Y B 4 4 Y C 4 9 5 5 D Y E 1 0 5 5 9 6 11 22 1 2 6 6 11 22 3 Y B 4 7 Y C 002916 002774 B 002775 C 002776 D E 002779 B...

Page 12: ...10 N1 N2 1 2 3 4 T1 N1 N2 5 2013 2015 2016 7 5 6 7 ON 8 AUTO 002826 C 002780 D E 002781 000135 10000003502 B 14 07 2017 Generac Power Systems Inc 2016 Generac Power Systems Inc Generac Power Systems I...

Reviews: