Generac Power Systems 04077-01, 04109-1, 04079-1, 00 Installation And Adjustment Manual Download Page 25

Generac

®

Power Systems, Inc. 23

Do not attempt manual transfer switch 
operation until all power voltage supplies to
the transfer switch have been positively turned
off. Failure to turn off all power voltage 
supplies will result in extremely hazardous 
and possibly fatal electrical shock.

4. Manually set the transfer switch to the STANDBY

position, i.e., load terminals connected to the

generator's E1/E2 terminals. The transfer switch

operating lever should be down.

5. Set the generator's Auto/Off/Manual switch to

MANUAL. The engine should crank and start

immediately.

6. Let the engine stabilize and warm up for a few

minutes.

7. Set the generator’s main circuit breaker to its ON

(or closed) position. Loads are now powered by

the standby generator.

8. Turn ON electrical loads. Apply an electrical load

equal to the full rated wattage/amperage capacity

of the installed generator.

9. Connect an accurate AC frequency meter across

terminal lugs E1 and E2. Voltage should be

greater than 230 volts; frequency should be

greater than 58 Hertz.

10. Let the generator run at full rated load for 20-30

minutes. Listen for unusual noises, vibration or

other indications of abnormal operation. Check

for oil leaks, evidence of overheating, etc.

11. When testing under load is complete, turn OFF

electrical loads.

12. Set the generator's main circuit breakers to their

OFF (or open) positions.

13. Let the engine run at no-load for a few minutes.
14. Set the Auto/Off/Manual switch to OFF. The

engine should shut down.

3.5 CHECKING 

AUTOMATIC 

OPERATION

To check the system for proper automatic operation,

proceed as follows:
1. Check that the Auto/Off/Manual switch is set

to OFF.

2. Manually set the transfer switch to the UTILITY

position, i.e., load terminals connected to the util-

ity power source side.

3. Turn ON the utility power supply to the transfer

switch, using the means provided (such as a util-

ity main line circuit breaker).

4. Set the Auto/Off/Manual switch to AUTO. The sys-

tem is now ready for automatic operation.

5. Turn OFF the utility power supply to the transfer

switch.

With the Auto/Off/Manual switch at AUTO, the engine

should crank and start when the utility source power

is turned OFF. After starting, the transfer switch

should connect load circuits to the standby side. Let

the system go through its entire automatic sequence

of operation.
With the generator running and loads powered by

generator AC output, turn ON the utility power sup-

ply to the transfer switch. The following should

occur:
• After about six seconds, the switch should transfer

loads back to the utility power source.

• About one minute after retransfer, the engine

should shut down.

3.6  ADJUSTING THE LOAD BLOCK

When the natural gas system is being used, the load

block is fitted with an adjustment screw that has

been calibrated to provide maximum power.

However, because of variations in the Btu content of

natural gas across the country, it may be necessary to

readjust the load block.
• Connect a frequency meter to the output of the

generator.

• Start the unit and apply full load according to the

following chart:

• Allow the unit to stabilize; then, turn the adjust-

ment screw slowly clockwise or counterclockwise

and watch the frequency.

• When the highest frequency is reached, turn the

adjustment screw counterclockwise 1/4 turn.

• The fuel system is now set.
• For LP gas operations, the hose and blanking plug

must be reconfigured as shown in Figure 1.3, Page

7. The unit is set to provide maximum power

using LP gas.

Do not make any unnecessary adjustments.
Factory settings are correct for most applica-
tions. However, when making adjustments, be
careful to avoid overspeeding the engine.

Section 3 — Post-installation Start-up Adjustments

Guardian Air-cooled Generators

Unit

120 Volts

240 Volts

6 kW 

(Non-SA)

:

50 amps

25 amps

8 kW 

(Non-SA)

:

66.7 amps

33.3 amps

10 kW 

(Non-SA)

: 83.3 amps

41.6 amps

Sound Attn.:

66.7 amps

33.3 amps

Summary of Contents for 04077-01, 04109-1, 04079-1, 00

Page 1: ...ustment Manual Air cooled Prepackaged Standby Generators Models Nonsound Attenuated Non SA 04077 1 6 kW 04109 1 8 kW 04079 1 10 kW Sound Attenuated SA 00789 1 8 kW 00844 1 8 kW ONLY QUALIFIED ELECTRIC...

Page 2: ...s symbol points out important safety informa tion that if not followed could endanger personal safety and or property of you and others This symbol points out potential explosion hazard This symbol po...

Page 3: ...5 1 16 Grounding the Generator 15 1 17 The Battery 16 1 17 1 Battery Installation 17 1 18 The Fuse 17 1 19 Post Installation Inspection 17 Section 2 Operation 18 2 1 Using the Auto Off Manual Switch 1...

Page 4: ...sufficient concentrations can cause unconsciousness or even death This exhaust sys tem must be installed properly in strict compli ance with applicable codes and standards Following installation you m...

Page 5: ...ediate medical help Never wear jewelry when working on this equip ment Jewelry can conduct electricity resulting in electric shock or may get caught in moving com ponents causing injury FIRE HAZARDS F...

Page 6: ...tion 85 John Street New York N Y 10038 7 AGRICULTURAL WIRING HANDBOOK available from the Food and Energy Council 909 University Avenue Columbia MO 65201 8 ASAE EP 3634 INSTALLATION AND MAINTE NANCE OF...

Page 7: ...s it may shift on lifting pipes during transportation which may result in injury The generator was not designed to be lifted by its roof Use the lifting holes or brackets provided near the base of the...

Page 8: ...st spark can ignite such fuels and cause an explosion No leakage of fuel is permitted Natural gas which is lighter than air tends to collect in high areas LP gas is heavier than air and tends to settl...

Page 9: ...rete pad Remove the packing material from the unit and unbolt the two 4 inch by 4 inch wooden blocks from the underside of the mounting base Plug the holes with the plugs provided Prepare the installa...

Page 10: ...8 Generac Power Systems Inc Figure 1 4 Generator and Transfer Switch Mounting Dimensions 6 kW 8 kW and 10 kW Non SA Section 1 Installation Guardian Air cooled Generators...

Page 11: ...Generac Power Systems Inc 9 Figure 1 4 Continued Section 1 Installation Guardian Air cooled Generators...

Page 12: ...10 Generac Power Systems Inc Figure 1 5 Generator Mounting Dimensions Sound Attenuated Section 1 Installation Guardian Air cooled Generators...

Page 13: ...ty is supply ing 120 240 volt single phase electrical service 1 9 TOTAL CIRCUIT ISOLATION METHOD If essential electrical loads cannot be grouped togeth er and wired into an emergency distribution pane...

Page 14: ...e a length of flexible conduit between the generator and any rigid conduit NOTE See also Emergency Circuit Isolation Method Section 1 8 and Total Circuit Isolation Method Section 1 9 on Page 11 1 11 1...

Page 15: ...Section 1 Installation Guardian Air cooled Generators Figure 1 10 Interconnection Diagram for Single Phase Power System Sound Attenuated Figure 1 9 Interconnection Diagram for Single Phase Power Syste...

Page 16: ...l module circuit board in the control panel Refer to the Operation section of this manual 1 13 CONTROL CIRCUIT INTERCONNECTIONS For 6 kw 8 kW and 10 kW units not including sound attenuated these inter...

Page 17: ...dip switches see Figure 1 12 which may be set up differently during installation 1 Dip switch 1 When in the ON position the board requires 20 Vac from the step down transformer to the control board t...

Page 18: ...of the battery and Disconnect charging source prior to connecting or dis connecting battery terminals Do not open or mutilate the battery Released electrolyte has been known to be harmful to the skin...

Page 19: ...black battery cable from frame ground to the battery post indicated by a nega tive NEG or Figure 1 14 Battery Cable Connections NOTE With the battery installed and utility power source voltage availab...

Page 20: ...el or during the normal exercise cycle To prevent possible injury that might be caused by such sudden starts always set the switch to OFF and remove the fuse before working on or around the generator...

Page 21: ...ts timing E Retransfer Time Delay This timer runs for about 15 SA six seconds At end of a 15 second SA six second delay circuit board action de energizes transfer relay in the transfer switch Retransf...

Page 22: ...uipped with the following systems that protect it against potentially damaging conditions 1 Low Oil Pressure Sensor 2 High Temperature Sensor 3 Overcrank 4 Overspeed On sound attenuated models there a...

Page 23: ...should be wired to the unit by a qualified electrician or Generac Guardian Authorized Dealer 2 Remote Common Alarm This allows for an alarm light horn etc to activate when any fault has occurred Lines...

Page 24: ...r switch and load circuit rat ings turn OFF the utility power supply to the transfer switch 5 Set the generator s main circuit breaker to its OFF or open position Initial tests will be con ducted at n...

Page 25: ...ing the means provided such as a util ity main line circuit breaker 4 Set the Auto Off Manual switch to AUTO The sys tem is now ready for automatic operation 5 Turn OFF the utility power supply to the...

Page 26: ...t to obtain 62 Hertz at no load 7 When frequency is correct at no load check the AC voltage reading If voltage is incorrect the volt age regulator may require adjustment Figure 3 1 6 kW Engine Governo...

Page 27: ...emove the roof to adjust the voltage regulator on nonsound attenuated units Figure 3 4 Voltage Adjustment Potentiometer NOTE The voltage regulator is housed in the generator s control panel The regula...

Page 28: ...s disconnected and then reconnected The exerciser WILL NOT work if dip switch 2 Remote Not Auto is ON 3 10 2 SOUND ATTENUATED UNITS The generator will start and exercise once every seven days During t...

Page 29: ...4 Replace control board The Auto Off Manual switch 1 Defective Auto Off Manual 1 Replace switch is set to OFF but the engine switch continues to run 2 Auto Off Manual switch 2 Check wiring and connect...

Page 30: ...LECTRICAL CONNECTIONS Complies with local code requirements and all National Electrical Codes Utility is connected and present Transfer switch is connected All wires running outside of the generator a...

Page 31: ...Generac Power Systems Inc 29 Section 5 Notes Guardian Air cooled Generators...

Page 32: ...Part No C4219 GENERAC POWER SYSTEMS INC P O BOX 8 WAUKESHA WI 53187 Revision 12 13 99 Printed in U S A...

Reviews: