Generac Power Systems 04077-01, 04109-1, 04079-1, 00 Installation And Adjustment Manual Download Page 23

2.5.3.1 Approximate Crank Cycle Times

• 15 seconds ON

• 15 seconds OFF

• 7 seconds ON

• 7 seconds OFF

• Repeat for 45 seconds

Approximately 90 seconds total

2.5.4 OVERSPEED

This feature protects the generator from damage by

shutting it down if it happens to run faster than the pre-

set limit. This protection also prevents the generator

from supplying an output that could potentially damage

appliances connected to the generator circuit. The over-

speed feature will activate as follows:
1. If the generator runs at 72 Hertz for five seconds,

the generator will shut down.

2. If the generator reaches 75 Hertz, it will shut

down instantly.

2.6 ADDITIONAL 

GENERATOR

FEATURES

2.6.1  6 KW, 8 KW AND 10 KW UNITS (NON-SA)

The standard 6 kW, 8 kW and 10 kW air-cooled

Guardians offer additional features that are not 

factory preset:
1. Remote Start – This allows for remote starting of

the generator by means of the #183 (common)

and #178 (normally open) lines with the

Auto/Off/Manual switch set to AUTO. Closure of

the circuit starts the unit; opening of the circuit

stops the unit. See Figure 2.5.

NOTE:

This function will work ONLY with the unit in the 
AUTO mode.

Figure 2.5 – Remote Start/Alarm Options

–Type 14 AWG wire is recommended.

–These options should be wired to the unit by a qualified electrician or

Generac/Guardian Authorized Dealer.

2. Remote/Common Alarm – This allows for an

alarm, light, horn, etc., to activate when any fault

has occurred. Lines #210 (common) and #211

(normally open) provide a “closure” on common

fault, which can be used for 120 volts, 10 amps

maximum. See Figure 2.5.

3. Remote Not Auto – The generator will not auto-

matically start during a utility failure.

2.6.2 SOUND ATTENUATED UNITS

Model 00844 of the sound attenuated air-cooled

Guardians offers additional features that are not factory

preset (see Figure 2.6):
1. Remote Start – This allows for remote starting of the

generator by means of the #183 and #178 lines with

the Auto/Off/Manual switch set to AUTO.

2. Engine Run Signal – The engine run signal is con-

trolled by the #14 line. The “volt free” engine run

signal relay closes when the #14 line is “hot.”

3. Automatic Transfer Switch (ATS) in Emergency –

For this to be active, a microswitch on the transfer

switch sends a signal along the #231 line to close

the “volt free” contact relay.

4. Shutdown Fault – This signal is controlled by the

main printed circuit board along the #229 line.

When a common fault occurs (low oil pressure,

high temperature, overspeed, overcrank), the

control board will send a signal along the #229

line to close the "volt free" contact relay.

Figure 2.6 – Remote Alarms

Section 2 — Operation

Guardian Air-cooled Generators

Generac

®

Power Systems, Inc. 21

Summary of Contents for 04077-01, 04109-1, 04079-1, 00

Page 1: ...ustment Manual Air cooled Prepackaged Standby Generators Models Nonsound Attenuated Non SA 04077 1 6 kW 04109 1 8 kW 04079 1 10 kW Sound Attenuated SA 00789 1 8 kW 00844 1 8 kW ONLY QUALIFIED ELECTRIC...

Page 2: ...s symbol points out important safety informa tion that if not followed could endanger personal safety and or property of you and others This symbol points out potential explosion hazard This symbol po...

Page 3: ...5 1 16 Grounding the Generator 15 1 17 The Battery 16 1 17 1 Battery Installation 17 1 18 The Fuse 17 1 19 Post Installation Inspection 17 Section 2 Operation 18 2 1 Using the Auto Off Manual Switch 1...

Page 4: ...sufficient concentrations can cause unconsciousness or even death This exhaust sys tem must be installed properly in strict compli ance with applicable codes and standards Following installation you m...

Page 5: ...ediate medical help Never wear jewelry when working on this equip ment Jewelry can conduct electricity resulting in electric shock or may get caught in moving com ponents causing injury FIRE HAZARDS F...

Page 6: ...tion 85 John Street New York N Y 10038 7 AGRICULTURAL WIRING HANDBOOK available from the Food and Energy Council 909 University Avenue Columbia MO 65201 8 ASAE EP 3634 INSTALLATION AND MAINTE NANCE OF...

Page 7: ...s it may shift on lifting pipes during transportation which may result in injury The generator was not designed to be lifted by its roof Use the lifting holes or brackets provided near the base of the...

Page 8: ...st spark can ignite such fuels and cause an explosion No leakage of fuel is permitted Natural gas which is lighter than air tends to collect in high areas LP gas is heavier than air and tends to settl...

Page 9: ...rete pad Remove the packing material from the unit and unbolt the two 4 inch by 4 inch wooden blocks from the underside of the mounting base Plug the holes with the plugs provided Prepare the installa...

Page 10: ...8 Generac Power Systems Inc Figure 1 4 Generator and Transfer Switch Mounting Dimensions 6 kW 8 kW and 10 kW Non SA Section 1 Installation Guardian Air cooled Generators...

Page 11: ...Generac Power Systems Inc 9 Figure 1 4 Continued Section 1 Installation Guardian Air cooled Generators...

Page 12: ...10 Generac Power Systems Inc Figure 1 5 Generator Mounting Dimensions Sound Attenuated Section 1 Installation Guardian Air cooled Generators...

Page 13: ...ty is supply ing 120 240 volt single phase electrical service 1 9 TOTAL CIRCUIT ISOLATION METHOD If essential electrical loads cannot be grouped togeth er and wired into an emergency distribution pane...

Page 14: ...e a length of flexible conduit between the generator and any rigid conduit NOTE See also Emergency Circuit Isolation Method Section 1 8 and Total Circuit Isolation Method Section 1 9 on Page 11 1 11 1...

Page 15: ...Section 1 Installation Guardian Air cooled Generators Figure 1 10 Interconnection Diagram for Single Phase Power System Sound Attenuated Figure 1 9 Interconnection Diagram for Single Phase Power Syste...

Page 16: ...l module circuit board in the control panel Refer to the Operation section of this manual 1 13 CONTROL CIRCUIT INTERCONNECTIONS For 6 kw 8 kW and 10 kW units not including sound attenuated these inter...

Page 17: ...dip switches see Figure 1 12 which may be set up differently during installation 1 Dip switch 1 When in the ON position the board requires 20 Vac from the step down transformer to the control board t...

Page 18: ...of the battery and Disconnect charging source prior to connecting or dis connecting battery terminals Do not open or mutilate the battery Released electrolyte has been known to be harmful to the skin...

Page 19: ...black battery cable from frame ground to the battery post indicated by a nega tive NEG or Figure 1 14 Battery Cable Connections NOTE With the battery installed and utility power source voltage availab...

Page 20: ...el or during the normal exercise cycle To prevent possible injury that might be caused by such sudden starts always set the switch to OFF and remove the fuse before working on or around the generator...

Page 21: ...ts timing E Retransfer Time Delay This timer runs for about 15 SA six seconds At end of a 15 second SA six second delay circuit board action de energizes transfer relay in the transfer switch Retransf...

Page 22: ...uipped with the following systems that protect it against potentially damaging conditions 1 Low Oil Pressure Sensor 2 High Temperature Sensor 3 Overcrank 4 Overspeed On sound attenuated models there a...

Page 23: ...should be wired to the unit by a qualified electrician or Generac Guardian Authorized Dealer 2 Remote Common Alarm This allows for an alarm light horn etc to activate when any fault has occurred Lines...

Page 24: ...r switch and load circuit rat ings turn OFF the utility power supply to the transfer switch 5 Set the generator s main circuit breaker to its OFF or open position Initial tests will be con ducted at n...

Page 25: ...ing the means provided such as a util ity main line circuit breaker 4 Set the Auto Off Manual switch to AUTO The sys tem is now ready for automatic operation 5 Turn OFF the utility power supply to the...

Page 26: ...t to obtain 62 Hertz at no load 7 When frequency is correct at no load check the AC voltage reading If voltage is incorrect the volt age regulator may require adjustment Figure 3 1 6 kW Engine Governo...

Page 27: ...emove the roof to adjust the voltage regulator on nonsound attenuated units Figure 3 4 Voltage Adjustment Potentiometer NOTE The voltage regulator is housed in the generator s control panel The regula...

Page 28: ...s disconnected and then reconnected The exerciser WILL NOT work if dip switch 2 Remote Not Auto is ON 3 10 2 SOUND ATTENUATED UNITS The generator will start and exercise once every seven days During t...

Page 29: ...4 Replace control board The Auto Off Manual switch 1 Defective Auto Off Manual 1 Replace switch is set to OFF but the engine switch continues to run 2 Auto Off Manual switch 2 Check wiring and connect...

Page 30: ...LECTRICAL CONNECTIONS Complies with local code requirements and all National Electrical Codes Utility is connected and present Transfer switch is connected All wires running outside of the generator a...

Page 31: ...Generac Power Systems Inc 29 Section 5 Notes Guardian Air cooled Generators...

Page 32: ...Part No C4219 GENERAC POWER SYSTEMS INC P O BOX 8 WAUKESHA WI 53187 Revision 12 13 99 Printed in U S A...

Reviews: