Section 2 – Installation

IMPACT-36 plus II Recreational Vehicle Generator

2.4.2 SOME IMPORTANT CONSIDERATIONS

When installing an LP gas system, consider seriously
the following items:

• All fittings, lines, hoses and clamps must be tight

and free of leaks. Apply a pipe sealant to threads
when assembling threaded connections. This
reduces the possibility of leakage.

Test the entire fuel system for leaks, using approved
test methods.

• Optimum gas pressure at the inlet to the gaseous

fuel solenoid valve and secondary regulator is 11
inches water column.

• The installer’s fuel supply connection point is at

the gaseous fuel solenoid valve. This is a 3/4 inch
(female) connection. Provide a suitable 3/4 inch
NPT (male) connector to attach to the fuel supply
line.

• Use a length of approved flexible fuel hose between

gaseous fuel solenoid valve and rigid gas piping.
The flexible line should be at least six (6) inches
longer than necessary.

2.4.3 VAPOR WITHDRAWAL

Liquid propane (LP) gas is stored in pressure tanks
as a liquid. The gas systems used with these genera-
tors were designed only for “vapor withdrawal” type
systems. Vapor withdrawal systems use the gas
vapors that form above the liquid fuel in the tank, Do
NOT attempt to use the kit along with any “liquid
withdrawal” type system.

2.4.4 PRIMARY REGULATOR

Gas pressure delivered to the solenoid valve must be
properly regulated by means of a primary gas regula-
tor. Mount the primary regulator at the gas tank out-
let or in the supply line from the gas tank, The fol-
lowing rules apply:

• For best results, the primary regulator supplies

gaseous fuel to the secondary regulator at 11 inch-
es water column. Do NOT exceed 14 inches water
column.

• The installer must be sure the primary regulator is

rated at sufficient gas flow to operate the generator
plus all other gas appliances in the circuit.

NOTE:

Recommended MINIMUM gas flow rate for all air-
cooled Impact-34 plus II series generators is 67
cubic feet per hour.

IMPORTANT:  IF AN EXISTING PRIMARY GAS REG-
ULATOR DOES NOT HAVE A SUFFICIENT FLOW
CAPACITY FOR THE GENERATOR AND OTHER
GAS APPLIANCES IN THE CIRCUIT, (a) INSTALL A
PRIMARY REGULATOR WITH ADEQUATE FLOW
RATE, OR (b) INSTALL A SEPARATE REGULATOR
RATED AT LEAST 67 CUBIC FEET PER HOUR. THE
INLET SIDE OF ANY PRIMARY REGULATOR THAT
SUPPLIES THE GENERATOR MUST CONNECT
DIRECTLY TO GAS TANK PRESSURE. DO NOT TEE
THE GENERATOR LINE INTO A GAS CIRCUIT
FEEDING OTHER APPLIANCES.

2.4.5 GASEOUS CARBURETION

LP gas vapors should be supplied to the generator
regulator inlet at about 11 inches water column (pos-
itive pressure). The engine piston draws air in during
the intake stroke (Figure 2.16). This air passes
through a carburetor venturi which creates a low
pressure that is proportional to the quantity of air
being pumped. The low pressure from the carburetor
venturi acts on the regulator diaphragm, to pull the
diaphragm toward the source of low pressure. A lever
attached to the diaphragm opens a valve to permit
gas flow through the carburetor.

The greater the air flow through the carburetor ven-
turi, the lower the pressure at the venturi throat, the
greater the diaphragm movement and the greater the
movement of the regulator valve. The more the regu-
lator valve opens, the greater the gas flow that is pro-
portional to air flow through the carburetor.

The following facts about the secondary regulator
must be emphasized:

Figure 2.16 — Propane Gas Carburetion Diagram

Summary of Contents for 00941-4

Page 1: ...Owner s Manual and Installation Instructions Air cooled Recreational Vehicle Generator Model No 00941 4 IMPACT 36 plus II with Inverter This manual should remain with the unit...

Page 2: ...f the vehicle and its equipment and for the safety of all vehicle occupants Before using this equipment we strongly recommend that the operator read this manual and thoroughly under stand all instruct...

Page 3: ...Air Intake Screen 11 3 7 Engine Spark Plug 11 3 8 Inverter 11 3 9 Cleaning the Generator 11 3 10 Battery 12 3 11 Service and Adjustments 12 3 12 Adjusting the Carburetor 12 3 13 Adjusting Valve Clear...

Page 4: ...MS MOVE INTO FRESH AIR IMMEDIATELY IF SYMPTOMS PERSIST GET MEDICAL HELP Shut down the generator and do not operate it until it has been inspected and repaired Never sleep in the vehicle while the gens...

Page 5: ...the victim from the live conductor AVOID DIRECT CONTACT WITH THE VICTIM Use a nonconduct ing implement such as a dry rope or board to free the victim from the live conductor If the victim is unconscio...

Page 6: ...Rating__________________________ 4 Rated Voltage __________________ 5 Phase ______________________________ 6 Hertz __________________________ 1 1 1 IMPACT 36LPG PLUS II FEATURES 1 Generator Air Intake...

Page 7: ...ion 1 General Information IMPACT 36 plus II Recreational Vehicle Generator 1 1 2 INVERTER FEATURES PART NO 0D4885 1 Inverter 2 12 Pin Connection 3 Customer AC Output 4 DC Input 5 Cooling Fan REFERENCE...

Page 8: ...y shorten its life Add up the rated watts of all electrical lighting appliance tool and motor loads the generator will power at one time This total should not be greater than the wattage capacity of t...

Page 9: ...ter control system the computer disables the load capability of the gen erator and shuts down the engine Do not attempt to physically adjust or control the engine speed Equipment damage or per sonal i...

Page 10: ...ENCES EXIST BETWEEN VEHICLES FOR EXAMPLE SOME VEHICLES MAY USE A TRANS FER SWITCH TO ISOLATE DOCKSIDE POWER FROM THE GENERATOR WHILE OTHER VEHI CLES MAY USE AN ISOLATING RECEPTACLE SOME VEHICLES MAY B...

Page 11: ...P UNITS These generators are equipped with a liquefied petro leum LP gas fuel system LP gas is usually supplied as a liquid in pressure tanks These generators require a vapor withdrawal type fuel syst...

Page 12: ...ne oil after the first 25 hours of opera tion Thereafter change oil every 100 operating hours Change oil more frequently if operating con sistently under heavy load or at high ambient tem peratures Wa...

Page 13: ...7 ENGINE SPARK PLUG Clean engine spark plug and set gap to 0 030 inch 0 76mm every 100 hours of operation Figure 3 5 Clean by scraping or wire brushing and washing with commercial solvent DO NOT BLAS...

Page 14: ...area immediately with clear water Do not use any jumper cables or booster bat tery to crank and start the generator engine If any battery has discharged remove it from the vehicle for recharging 3 11...

Page 15: ...unning drain the oil completely Refill crankcase with recom mended oil See Specifications Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase Remove spar...

Page 16: ...14 Generac Power Systems Inc Section 4 Notes IMPACT 36 plus II Recreational Vehicle Generator...

Page 17: ...PART II INSTALLATION INSTRUCTIONS ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION DANGER...

Page 18: ...nds that the installation initial startup and maintenance of this equipment is carried out by a Generac Authorized Service Dealer The engine exhaust fumes contain carbon monox ide which can be DEADLY...

Page 19: ...conductor If the vic tim is unconscious apply first aid and get immediate medical help Never wear jewelry when working on this equip ment Jewelry can conduct electricity resulting in electric shock or...

Page 20: ...ed standards as well as the manufacturer s recommendations The following standards booklets latest revision are available from the sources indicated 1 NFPA 1192 Standard for Recreational Vehicles repl...

Page 21: ...ich will restrain the generator set should consist of at least two horizontal beams These beams should consist of a 1 1 2 inch square 11 gauge steel tubing OR b 1 1 2 inch 11 gauge angle iron A typica...

Page 22: ...STEEL DUE TO ALUMINUM S LOW MELTING POINT If the compartment is lined with galvanized steel it may be constructed of any material Generac rec ommends that the compartment be constructed of 1 2 inch t...

Page 23: ...ing the vehicle interior Refer to the sealant information as noted previously NOTE Silicone rubber base sealant is an acceptable caulking material Pressing putty tape onto com partment joints and seam...

Page 24: ...is used its coated side should face toward the compartment interior Using a combination of sound insulating materials can often reduce noise more effectively than a single material For example a sheet...

Page 25: ...e the compartment door interior except for air openings with suitable fire proof sound insula tion such as 1 inch thick fiberglass with a 2 pound density It is absolutely essential that an adequate fl...

Page 26: ...F PLANNING TO INSTALL THE GEN ERATOR IN A COMPARTMENT BE SURE TO LEAVE AT LEAST ONE INCH 2 recommended OF CLEAR ANCE BETWEEN THE GENERATOR AND COM PARTMENT WALLS AND CEILING INCLUDE 26 GAUGE GALVANIZE...

Page 27: ...AS THE GENERATOR The sensing harnesses supplied with the inverter have a maximum length of 12 feet If the cables are longer than needed coil the excess near the inverter unit If a greater length is n...

Page 28: ...o the secondary regulator at 11 inch es water column Do NOT exceed 14 inches water column The installer must be sure the primary regulator is rated at sufficient gas flow to operate the generator plus...

Page 29: ...be tested under gas or air pressure of not less than 90 psi 620kPa while using soap and water or equiva lent solution to check for leaks Other approved methods of testing for leaks may be used if app...

Page 30: ...vehicle Terminate the exhaust tailpipe such that exhaust gases will not be drawn back into the generator compartment and recirculated If there is any possibility of the tailpipe or muffler being damag...

Page 31: ...om being connected to two different power sup plies at the same time such as generator and dockside power Conductors must be rated 221 F 105 C or must be of a larger conductor size 2 6 2 GENERATOR AC...

Page 32: ...gure 2 20 Transfer Switch Isolation Method Figure 2 21 Installation with Isolation Receptacle INVERTER INVERTER POWER CORD FOR DOCKSIDE POWER POWER SUPPLY CORD Section 2 Installation IMPACT 36 plus II...

Page 33: ...y rated 70 amp hours and capa ble of delivering 400 cold cranking amperes For prevailing ambient temperatures below 32 F 0 C use a battery rated 95 amp hours and capa ble of delivering 450 cold cranki...

Page 34: ...PLUG IN RECEPTACLE A plug in receptacle Figure 2 24 is provided on the generator set near the DC power wires Use this receptacle to connect an optional remote mounted start stop panel to the generator...

Page 35: ...l lines have to be primed Use of the Primer Switch on gasoline units will shorten this time 3 Let the engine warm up for about five minutes to allow internal temperatures to stabilize 4 Carefully insp...

Page 36: ...s properly and safely installed ELECTRICAL CONNECTIONS Connections comply with local code requirements and all National Electrical Codes Junction box is properly installed Wiring meets all standards A...

Page 37: ...ugh 1 Air cleaner plugged or damaged 1 Clean or replace as needed 2 Defective spark plug 2 Clean regap or replace plug Engine starts shuts down 1 Engine oil is low 1 Check oil add as needed when Start...

Page 38: ...36 Generac Power Systems Inc Section 5 Electrical Data IMPACT 36 plus II Recreational Vehicle Generator Wiring Diagram and Schematic Drawing No 0D4947 B...

Page 39: ...Generac Power Systems Inc 37 Section 5 Electrical Data IMPACT 36 plus II Recreational Vehicle Generator Wiring Diagram and Schematic Drawing No 0D4947 B...

Page 40: ...22 2 9 13 2 11 21 14 40 9 15 1 19 19 17 14 16 46 23 8 9 5 41 9 20 41 31 38 25 43 27 26 7 12 31 42 22 37 22 10 30 20 48 33 34 45 24 51 50 Section 6 Exploded Views and Parts Lists IMPACT 36 plus II Rec...

Page 41: ...089744 1 RESISTOR POWER 1 OHM 29 0A6423A 2 BUS BAR OUTER 30 045756 4 TAPTITE M6 1 0 X 10MM 31 086722 1 BRACKET HEAT SINK PCB 32 075210A 1 TERMINAL BLOCK 33 0A6423B 4 BUS BAR INNER 34 0912970025 1 GROU...

Page 42: ...52 9 56 49 50 48 9 54 51 44 42 2 62 61 47 11 9 16 49 9 45 46 1 11 18 9 3 19 4 4 3 5 12 21 22 6 2 7 5 13 14 13 58 5 15 16 7 8 5 63 Section 6 Exploded Views and Parts Lists IMPACT 36 plus II Recreationa...

Page 43: ...X 35mm 33 020668 2 EARTHING STRAP ITEM PART NO QTY DESCRIPTION 34 092000 1 BRACKET MUFFLER HANGER 35 079246 2 SCREW HHC M6 1 0 X 16mm W LOCK WASHER 36 086731A 1 ASSEMBLY MUFFLER 37 094670 1 CLAMP EXH...

Page 44: ...49 50 34 28 13 52 8 1 18 17 51 25 22 33 32 58 42 19 59 23 24 11 13 37 17 4 39 40 38 21 26 30 53 31 48 43 45 46 44 47 36 Section 6 Exploded Views and Parts Lists IMPACT 36 plus II Recreational Vehicle...

Page 45: ...HHFC M8 1 25 X 35 30 0C3733 2 RETAINER VALVE 31 0C4390 2 SPRING VALVE 32 088590 1 DOWEL DIA 12 X 18L 33 083152 1 GEROTER INNER 6 5 34 076381 2 BOLT CON ROD 36 021705B 1 ASSY CYL HD GDS STS 37 0C3590 1...

Page 46: ...68 60 4 73 67 72 42 41 45 44 66 65 57 75 7 58 56 63 64 32 43 48 49 38 37 35 47 60 51 53 54 52 62 61 59 59 31 34 36 50 16 13 30 32 85 84 66 89 87 88 86 66 83 Section 6 Exploded Views and Parts Lists IM...

Page 47: ...3 8 16 X 1 1 4 ITEM PART NO QTY DESCRIPTION 46 086705 1 PLATE DIVIDER 47 090192 1 WASHER CARBURETOR 48 089477 1 CLIP ADJUSTMENT 49 086706 1 ROD THROTTLE CONTROL 50 089478 1 SNAP RETAINING 51 078609 2...

Page 48: ...SPRING REGULATOR 45N M 29MM 16 0C4643A 1 INLET TWIN REG 11 11 DIA 17 0C6066 1 SEAL INLET REGULATOR 18 0C5968 1 SUPPORT INLET SEAL 19 0C5759 1 PIN PIVOT ARM 20 0C5761 1 LEVER REGULATOR 21 0C6069 1 GAS...

Page 49: ...Section 7 Installation Diagram IMPACT 36 plus II Recreational Vehicle Generator Major Features and Dimensions Drawing No 0F1119 Generac Power Systems Inc 47...

Page 50: ...your engine or a part component thereof has failed due to abuse neglect improper maintenance or unap proved modifications or the use of counterfeit and or grey market parts not made supplied or appro...

Page 51: ...Any such emissions related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emi...

Page 52: ...anty expense allowances are subject to the conditions defined in Guardian s Warranty Policies and Procedures Guide THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING Generac Guardian generators that utili...

Reviews: