Owner’s Manual for G4-ECO Light Tower
21
Operation
Section 3: Operation
Operation Configuration
(000145)
DANGER
Electrocution. In the event of electrical accident,
immediately shut power OFF. Use non-conductive
implements to free victim from live conductor. Apply
first aid and get medical help. Failure to do so will
result in death or serious injury.
(000152)
DANGER
Electrocution. Verify electrical system is
properly grounded before applying power.
Failure to do so will result in death or serious
injury.
(000104)
DANGER
Electrocution. Water contact with a power
source, if not avoided, will result in death
or serious injury.
(000353)
DANGER
Asphyxiation. Do not connect any engine-powered
equipment or fired air heaters to theconvenience
receptacle(s), even with properventilation. Carbon
monoxide, if not avoided, will result in death or
serious injury.
NOTE:
For grounding requirements, follow local, state,
oil and gas or petrochemical plant grounding, MSHA,
OSHA, CSA, IEC, IEEE, NFPA, ABS Marine and
Maritime guidelines as applicable. See
Before setting up the light tower determine if the unit will
require utility input power or will export power to
additional light towers.
•
If utility power will be used connect a 120/240
VAC-20A power supply with an L14-20P
connection to the control panel shore power input.
•
If export power is required for an additional light
tower, connect a connect a 120/240VAC-20A
power supply with a L14-20P connection to the
control panel shore power output.
NOTE:
Shore power cords are not included with this unit
and must be supplied by the end user. See
recommended cable size and length.
Table 3 - Recommended Shore Power Cable Size and
Length
Maximum Distance - G4-ECO to PLT240
CONFIG L5-20R to L520P/5-15P
Maximum Distance
One Unit LINK/CTF
Cable
Size
Extension Cord
300 ft (91.4 m)
10/3
L5-20P – L5-20R
L5-20P – 5-15R
200 ft (61 m)
12/3
L5-20P – L5-20R
L5-20P – 5-15R
G4-ECO 1 to G4-ECO 2
CONFIG L14-20R to L14-20P
Maximum Distance
Cable
Size
Extension Cord
500 ft (152.4 m)
10/3
L14-20P --- L14-20R
300 ft (91.4 m)
12/3
L14-20P --- L14-20R
Utility Power to G4-ECO 1
CONFIG L14-20R to L14-20P
Maximum Distance
Cable
Size
Extension Cord
150 ft (45.7 m)
10/3
L14-20P --- L14-20R
100 ft (30.5 m)
12/3
L14-20P --- L14-20R
G4-ECO 1 to G4-ECO 2
CONFIG L14-20R to L14-20P
Maximum Distance
Cable
Size
Extension Cord
150 ft (45.7 m)
10/3
L14-20P --- L14-20R
100 ft (30.5 m)
12/3
L14-20P --- L14-20R
Summary of Contents for G4-ECO
Page 32: ...28 Owner s Manual for G4 ECO Light Tower Operation This page intentionally left blank ...
Page 39: ...Owner s Manual for G4 ECO Light Tower 35 Section 6 Wiring Diagrams AC Schematic ...
Page 40: ...36 Owner s Manual for G4 ECO Light Tower Wiring Diagrams GTL04 Controller ...
Page 41: ...Owner s Manual for G4 ECO Light Tower 37 Wiring Diagrams DC Schematic ...
Page 42: ...38 Owner s Manual for G4 ECO Light Tower Wiring Diagrams LED Light Wiring ...
Page 43: ......