22 / 29
1436 cPos
®
Profinet
5.6.16 Find Function
This action determines the valve control function and the air flow through the internal pilot valves. If control function 2 is
determined, the GEMÜ 1436 cPos
®
switches the open and closed position so that the display does not correspond in any way to
the closed position but completely corresponds to the open position.
Request from the master:
0xYY
0x41 ("A")
0x00, 0x07
Function
1 byte
1 byte
2 bytes
4 bytes
Function:
Activate "Find Function"
0x00,0x00,0x00,0x01
Cancel "Find Function"
0x00,0x00,0x00,0x02
Response from the GEMÜ 1436 cPos
®
:
0xYY
0x41 ("A")
0x00, 0x07
Status
1 byte
1 byte
2 bytes
4 bytes
The status reported is the current valve function selected.
Status:
"Find Function" inactive
0x00,0x00,0x00,0x01
Approach the start position
0x00,0x00,0x00,0x02
Output the test pattern
0x00,0x00,0x00,0x03
Action cannot be started
0x01, 0x00, 0x00, 0x00
5.6.17 Adjust Time
This action moves the valve into the closed and open position, and determines the opening and closing times while doing so.
Request from the master:
0xYY
0x41 ("A")
0x00, 0x08
Function
1 byte
1 byte
2 bytes
4 bytes
Function:
Activate "Adjust Time"
0x00,0x00,0x00,0x01
Cancel "Adjust Time"
0x00,0x00,0x00,0x02
Acknowledge error
0x00,0x00,0xFF,0x00
Response from the GEMÜ 1436 cPos
®
:
0xYY
0x41 ("A")
0x00, 0x08
Status
1 byte
1 byte
2 bytes
4 bytes
The status reported is the current valve function selected.
Status:
"Adjust Time" inactive
0x00, 0x00, 0x00, 0x01
Approach the start position
0x00, 0x00, 0x00, 0x02
GEMÜ 1436 cPos
®
measures the "go Close"
time
0x00, 0x00, 0x00, 0x03
GEMÜ 1436 cPos
®
measures the "go Open"
time
0x00, 0x00, 0x00, 0x04
Error 22 active
0x00, 0x00, 0x16, 0xFE
Error 22 acknowledged
0x00, 0x00, 0x16, 0xFF
Action cannot be started
0x01, 0x00, 0x00, 0x00