Step Ten

I. Programming REV mA (Optional): 

 In factory default, 

t

he 

transmitter operates with 4 mA at the maximum range (MaxR), and 

20 mA at the dead band (MinR). Using the menu item REV mA, you 

can change the unit to reverse this to 20 mA at the furthest distance 

(MaxR) and 4 mA at the closest distance (MinR). 

NOTE: You must set HEIGHT and FULL R prior to reversing the 
4 and 20 mA.  Regardless of which mode you are in (Norm or 
Rev), changes to the HEIGHT or FULL R are always with 
respect to the original settings programmed.

NOTE: Any changes to the HEIGHT will effect the FULL R 
value.  The FULL R will stay at the same physical level in the 
tank.  An increase to the HEIGHT value will result in an equal 
increase to the FULL R value.  A decrease to the HEIGHT value 
will result in an equal decrease to the FULL R value.

Step Eleven

PROGRAMMING

SELECT

FAST

SELECT

FAST

SELECT

FAST

4 mA

20 mA

20 mA

4 mA

Normal mA Mode

MaxR (4 mA) set at empty tank 

and MinR (20 mA) set at full tank. 

Reverse mA Mode

MaxR (20 mA) set at empty tank 
and MinR (4 mA) set at full tank. 

PROGRAMMING

G. Programming HEIGHT:  

To change HEIGHT 4 mA value.

1.  Press the SELECT/FAST button and hold it for 5 seconds until 

PROG appears.

2.  When TANK appears, press the SELECT/FAST button. The dis-

play will rotate between HEIGHT, FILL H and REV mA.

3.  When HEIGHT appears, press the SELECT/FAST button. The 

display will show a decimal reading in the selected UNITS. 

4.  Press the UP/DOWN buttons to increase or decrease this value to the 

distance from the transducer face to the bottom of the tank.  NOTE: 
Simultaneously holding down the SELECT/FAST button while press-
ing the UP or DOWN button will increase the speed of the display. 

5.  When you have reached the desired value, press SELECT/FAST 

to SAVE.

H. Programming FILL H:

 To change FILL H 20 mA value.

1.  Press the SELECT/FAST button and hold it for 5 seconds until 

PROG appears.

2.  When TANK appears, press the SELECT/FAST button. The dis-

play will rotate between HEIGHT, FILL H and REV mA.

3.  When FULL H appears, press the SELECT/FAST button. The 

display will show a decimal reading in the selected UNITS. 

4.  Press the UP/DOWN buttons to increase or decrease this value to 

the distance from the bottom of the vessel to the full point (typi-
cally the straight wall height). 

5.  When you have reached the desired value, press SELECT/FAST 

to SAVE it.

You have successfully programmed the FILL H or 20mA value.

NOTE: You can increase the speed at which the display changes 
by pressing the SELECT/FAST button while simultaneously hold-
ing down the UP or DOWN button.

SELECT

FAST

SELECT

FAST

SELECT

FAST

UP

DOWN

SELECT

FAST

SELECT

FAST

SELECT

FAST

UP

DOWN

Summary of Contents for UCL-520

Page 1: ...d include original packing slip C O D returns are not accepted Gems reserves the right to apply restocking charges Gems further reserves the right to unilaterally waive this warranty and to dispose of...

Page 2: ...ut 4 20 mA two wire Signal invert 4 20 mA 20 4 mA Calibration Push button Fail safety Selectable 4 mA 20 mA 21 mA 22 mA or hold last value Process temp F 4 to 140 C 20 to 60 Temp comp Automatic Electr...

Page 3: ...iring and Electrical A supply voltage loop power of 12 28 VDC is used to power the UCL 520 transmitter The sensor circuit should never exceed a maximum of 28 volts DC Electrical wiring of the sensor s...

Page 4: ...ort period of time this message will disappear and be replaced by a numeric value B FULL Level has reached the programmed FULL set point C EMPTY Level has reached the programmed EMPTY set point D UNIT...

Page 5: ...POWER Displays the present acoustic power level AA MOUNT Displays either QUIET no fitting noise or NOISY potential fitting noise If NOISY with transmitter performance issues please contact Gems to di...

Page 6: ...MinR E Change Display Mode To change the display to indicate the height of liquid follow the instructions below 1 Press the SELECT FAST button and hold it for 5 seconds until PROG appears 2 When UNITS...

Page 7: ...LECT FAST button The dis play will rotate between HEIGHT FILL H and REV mA 3 When HEIGHT appears press the SELECT FAST button The display will show a decimal reading in the selected UNITS 4 Press the...

Page 8: ...ique that allows the user to enter the present distance from the transducer face to the liquid or a reflective target as the 20 mA FULL set point EMPTY Target calibration technique that allows the use...

Page 9: ...in a 2 5 cm riser 3 Stand Pipe A stand pipe may be used to dampen turbulence or separate surface foam Select a minimum 3 pipe for the stand pipe The pipe length should run the measure ment span Cut a...

Page 10: ...FAST SELECT FAST SELECT FAST TROUBLESHOOTING Transmitter UCL 520 4 mA Setting 26 2 8m 20 mA Setting 8 20 cm Factory Set Points Power Supply Power Supply 20 mA 4 mA mA 4 5 6 mA 19 20 21 Red Black Red...

Reviews: