B. Entering the Program Mode:
Press
and hold the
SELECT/FAST button for approximately 5 seconds until the display
changes from a numeric value to PROG, indicating that you have
entered the PROG mode.
Note: When PROG mode is active, the UCL-520 will hold the
last current value. The value will not change until the transmit-
ter is returned to RUN Mode.
Step Six
MENU ITEMS
N. FULL:
Target calibration technique that allows the user to enter
the present distance from the transducer face to the liquid or a reflec-
tive target as the 20 mA (FULL) set point
O. EMPTY:
Target calibration technique that allows the user to
enter the present distance from the transducer face to the liquid or a
reflective target as the 4 mA (EMPTY) set point.
P. WAIT:
Indicates that you have selected either FULL or EMPTY
and the transmitter is calculating the distance value.
Q. VALUES:
Allow the user to view the present calibration settings
that are programmed in the transmitter.
R. SETUP:
Displays the present calibration settings such as UNITS,
MinR, MaxR, and SAFE.
S. MINR:
The lesser distance from the transducer to the full tank
height of liquid.
T. MAXR:
The greater distance from the transducer to the empty tank
height of liquid.
U. RESET:
Allows the user to reset the transmitter to its original
factory default settings.
V. DIAG (Diagnostics):
Allows the user to view the present val-
ues of LEVEL, TEMP, ECHO, POWER, MOUNT and VER.
W. LEVEL
:
Displays the current Inch, Centimeter or Percent mea-
sured value.
X. TEMP:
Displays the temperature in the vessel at the transducer.
Y. ECHO:
Displays the present acoustic signal strength.
Z. POWER:
Displays the present acoustic power level
AA. MOUNT:
Displays either QUIET (no fitting noise) or NOISY
(potential fitting noise), If NOISY with transmitter performance
issues, please contact Gems to discuss your installation.
BB. VER (VERSION):
Displays the transmitter software version.
CC. DONE:
Indicates that the new value has been saved in memo-
ry (after depressing the SELECT/FAST key).
DD. ERROR:
Indicates that the new value has NOT been saved in
memory (after depressing the SELECT/FAST or EXIT key).
EE. RUN:
When displayed, if the user depresses the SELECT/FAST
key, the transmitter will exit the programming mode and return to the
RUN mode for normal operation.
FF. UP / DOWN:
Increases or decreases the SET 20 and SET 4
display values in the programming mode. NOTE: Simultaneously
holding down the SELECT/FAST button while pressing the UP or
DOWN button will increase the speed of the display.
Step Seven
PROGRAMMING
A. Introduction:
The transmitter has two modes, RUN and
PROGRAM. In the RUN mode, the transmitter is operational and the
display will indicate the liquid height in inches, centimeters or per-
cent.
In the PROGRAM mode, the display will indicate the selected mode
of calibration. The transmitter arrives from the factory with its set-
tings at 4 mA = maximum range and 20 mA = minimum range
(defined by the dead band or minimum measurement distance). The
transmitter is programmed with it’s built-in display and three button
keyboard.
Under normal application circumstances, users typi-
cally program the HEIGHT distance value, FILL H distance
value and FAIL-SAFE mode.
+
UP
DOWN
SELECT
FAST
UCL-520
--
+
UP
DOWN
SELECT
FAST
UCL-520
--
Hold for
5 Seconds
Top Menu
After entering the PROG mode, the display will scroll through the top
menu, alternately flashing UNITS, TANK, SAFE, TG CAL, VALUES,
HELP and RUN.