GEMO

PROGRAMMING HEAT SET

(ON-OFF CONTROL)

ON-OFF is active when 

“H.hys”

 is other then 0

PID PARAMETERS

- P, PI, PD, PID

 is active when 

“H.hys”

 is set to 0.

- PbC: 

Proportional band in oC.

- Ct: 

Control period for PID control. Prefer 4-10 sec.

- Ti:

 Integral time; Set in minutes. Determines how fast controller reacts to compensate the offset between SET point and the 

process value. If set to 0, integral part is OFF. If set too low, process value may oscillate.
-

 Td:

 Derivative time; Set in minutes. If set to 0, derivative part is OFF. Determines how sensitive the controller is to changes of 

the offset between SET point and the process value. If set too high, process value may oscillate or overshoot.

CLAEANING

Do not use any solvents (alcohol, thinners, benzine, acid, etc.) or corrosive substances to clean the device. Use only a dry 
and clean non-abrasive cloth. Before cleaning, disconnect the power supply and mains connections.