12/13
50
•
CAN bus
OptiMove CR07
Setting the user address (ID Number)
1. To enter the system parameter mode, press and hold the
key for 5 seconds. The LEDs
L1-L3
illuminate
2. Select the parameter
P12
on the display
A1
by using the
keys
3. Select an address between
1
and
127
on the display
A2
using
the
keys
4. Press
the key, in order to exit the system parameter mode
WARNING:
The selected address in the system parameter P12 may never be
"0", the address must be unique and may not conflict with the
numbers of other existing users!
Setting the Baud rate
1. To enter the system parameter mode, press and hold the
key for 5 seconds. The LEDs
L1-L3
illuminate
2. Select the parameter
P11
on the display
A1
by using the
keys
3. Select a value between
0
and
7
on the display
A2
using the
keys
Set value - P11
CAN Baud rate
0 20
kBit/s
1 50
kBit/s
2 100
kBit/s
3
125 kBit/s (Default)
4 250
kBit/s
5 500
kBit/s
6 800
kBit/s
7 1
Mbit/s
The Baud rate is selected with 125 kBits as default. This setting permits a
maximum cable length of approx. 500 m from the first to the last CAN bus
client. If longer cables are used, select a lower Baud rate.
4. Press
the key, in order to exit the system parameter mode