11.4.21 Function digital output 2
The output function can be set with the
Function digital output 2
parameter.
Index Sub-
In-
dex
Off-
set
Access
Rights
Length
Index name
Parameter
Type
Default
Values
0x4D
0
0
R/W
2 bits
Function digital
output 2
uint:8
2
0
1
2
3
Description of parameter values
Index name
Parameter
Values
Description
Function
digital output
0
(Output Open)
Signal is output with the corresponding valve
position. Detection of Open depends on the setting of the
parameter
Position Feedback
(index 0x51 (see “Actuator po-
sition feedback“, page 45)) and a correct initialization.
1
(Output Close)
Signal is output with the corresponding valve
position. Detection of Close depends on the setting of the
parameter
Position Feedback
(index 0x51 (see “Actuator po-
sition feedback“, page 45)) and a correct initialization.
2
(Output Error)
Only output error detection.
3
(Output Error & Warning)
Output error and warnings.
11.4.22 Logic digital inputs / outputs
The inputs and outputs can be inversed with the
Logic digital inputs/outputs
parameters.
Index Sub-
In-
dex
Off-
set
Access
Rights
Length
Index name
Parameter
Type
Default
Values
0x4E
1
0
R/W
1 bit
Logic digital
inputs / outputs
Input 1
Boolean
0
0
1
2
1
R/W
1 bit
Input 2
Boolean
0
0
1
3
2
R/W
1 bit
Input / output 1
Boolean
0
0
1
4
3
R/W
1 bit
Output 2
Boolean
0
0
1
Description of parameter values
Index name
Parameter
Values
Description
Logic digital inputs /
outputs
Input 1
0
(Active high)
Input 1
not
inversed.
1
(Active low)
Input 1 inversed.
Input 2
0
(Active high)
Input 2
not
inversed.
1
(Active low)
Input 2 inversed.
Input / output 1
0
(Active high)
Input/output
not
inversed.
1
(Active low)
Input/output inversed.
Output 2
0
(Active high)
Output
not
inversed.
1
(Active low)
Output inversed.
www.gemu-group.com
42 / 63
GEMÜ R639 eSyStep
Positioner (Code S0)
11 Specific data IO-Link (pin 6)