Index Sub-
Index
Access
rights
Index name
Parameter
Function
Factory
settings
Setting options
3
R/W
Force initialization Force during initial-
ization, dependent
on valve used
1 … 6
0xB0
1
R/W
Control parameters
P amplification
P component – po-
sitioner
200
1 … 200
(0.1 … 20.0)
2
R/W
D amplification
D component – po-
sitioner
10
1 … 200
(0.1 … 20.0)
3
R/W
Derivative time
Delay constant
0
0 to 100
(0 to 100 s)
4
R/W
Dead band
Permissible system
deviation
10
1 … 250
(0.1 … 25.0 %)
0xB2
1
R/W
Open / close tight
Open tight
Sealing function
valve position OPEN
995
800 … 1000
(80.0 … 100.0 %)
2
R/W
Close tight
Sealing function
valve position
CLOSED
5
0 … 200
(0 … 20.0 %)
0xB4
1
R/W
Split range
Split start
Set set value start
0
0 to Split End – 100
(0.0 to Split End –
10.0%)
2
R/W
Split end
Set set value end
1000
Split Start + 100 to
1000
(Split Start + 10.0%
to 100.0%)
0xB6
1
R/W
Stroke limiter
Max pos
Stroke limiter valve
position OPEN
1000
Min Pos to 1000
(Min Pos to
100.0%)
2
R/W
Min pos
Stroke limiter valve
position CLOSED
0
0 to Max Pos
(0.0% to Max Pos)
0xB8
1
R/W
Set value (W) input
Direction
Set value direction
set value input
0
0
→
Rise (rising)
1
→
Fall (falling)
2
R/W
Type
Determine signal in-
put
1
0
→
0 to 20 mA
1
→
4 to 20 mA
2
→
0 to 10 V
3
R/W
I min
Determine minimum
current input
35
0 to 40
(0 to 4.0 mA)
4
R/W
I max
Determine max-
imum current input
205
200 to 220
(20.0 to 22.0 mA)
5
R/W
U max
Determine max-
imum current input
103
100 to 110
(10.0 to 11.0 V)
0xBA
1
R/W
Analog output
Direction
Set value direction
set value output
0
0
→
Rise (rising)
1
→
Fall (falling)
2
R/W
Type
Determine signal
output
1
0
→
0 to 20 mA
1
→
4 to 20 mA
2
→
0 to 10 V
3
R/W
Min.
Determine minimum
signal output
0
0 to Max
(0.0% to Max)
4
R/W
Max
Determine max-
imum signal output
1000
Min to 1000
(Min to 100%)
GEMÜ R639 eSyStep
Positioner (Code S0)
www.gemu-group.com
33 / 63
11 Specific data IO-Link (pin 6)