16 Troubleshooting
Error
Possible cause
Troubleshooting
The product leaks downstream (doesn't
close or doesn't close fully)
Operating pressure too high
Operate the product with operating
pressure specified in datasheet
Valve body leaks or is damaged
Check valve body for potential damage,
replace valve body if necessary
The product doesn't close or doesn't
close fully
The actuator design is not suitable for the
operating conditions
Use an actuator that is designed for the
operating conditions
Foreign matter in the product
Remove and clean the product
Voltage is not connected
Connect voltage
The product doesn't open or doesn't open
fully
Actuator defective
Replace the actuator
Operating pressure too high
Operate the product with operating
pressure specified in datasheet
Foreign matter in the product
Remove and clean the product
The actuator design is not suitable for the
operating conditions
Use an actuator that is designed for the
operating conditions
Voltage is not connected
Connect voltage
Cable ends incorrectly wired
Wire cable ends correctly
The product leaks between actuator and
valve body
Bolting between valve body and actuator
loose
Retighten bolting between valve body and
actuator
Actuator/valve body damaged
Replace actuator/valve body
The product leaks between actuator
flange and valve body
Mounting parts loose
Retighten mounting parts
Valve body / actuator damaged
Replace valve body/actuator
Body of the GEMÜ product is leaking
Body of the GEMÜ product is faulty or
corroded
Check the body of the GEMÜ product for
potential damage, replace body if
necessary
Incorrect installation
Check installation of valve body in piping
Valve body connection to piping leaks
Incorrect installation
Check installation of valve body in piping
LED 1 is not lit
No initialisation
Initialise valve
Supply voltage too low
Check supply voltage
LED 1 lights up yellow
Set value signal outside of the area
Check set value signal
Temperature error
Check temperature
LED 1 flashes yellow
Actual value signal outside of the area
Check actual value signal
LED 1 and 2 are flashing yellow and red
simultaneously
No calibration
Contact GEMÜ
Internal error
Contact GEMÜ
16 Troubleshooting
www.gemu-group.com
29 / 34
GEMÜ 539