![GEM 539 eSyDrive Operating Instructions Manual Download Page 14](http://html1.mh-extra.com/html/gem/539-esydrive/539-esydrive_operating-instructions-manual_2206248014.webp)
5.6 Electrical data
Supply voltage:
Actuator size 0
Actuator size 1
Actuator size 2
Voltage
Uv = 24 V DC ± 10%
Rating
Max. 28 W
Max. 65 W
Max. 120 W
Operating mode
(OPEN/CLOSE
operation)
Continuous duty
Operating mode
(control operation)
Class C acc. to EN 15714-2
Reverse battery
protection
Yes
5.6.1 Analogue input signals
5.6.1.1 Set value
Input signals:
0/4 - 20 mA; 0 – 10 V DC (selectable using software)
Input type:
passive
Input resistance:
250 Ω
Accuracy/linearity:
≤ ±0.3% of full flow
Temperature drift:
≤ ±0.1% / 10°K
Resolution:
12 bit
Reverse battery
protection:
No
Overload proof:
Yes (up to ± 24 V DC)
5.6.1.2 Process actual value
Input signals:
0/4 - 20 mA; 0 – 10 V DC (selectable using software)
Input type:
passive
Input resistance:
250 Ω
Accuracy/linearity:
≤ ±0.3% of full flow
Temperature drift:
≤ ±0.1% / 10°K
Resolution:
12 bit
Reverse battery
protection:
No
Overload proof:
Yes (up to ± 24 V DC)
www.gemu-group.com
14 / 34
GEMÜ 539
5 Technical data