GEMÜ 1441 cPos-X
Number
Parameter Description Settings
Initial set-
ting
S01
Switching
cycle
counter
Number of
switching
cycles can
be reset by
the cus-
tomer
0 to
214748360
0
0 (is adjus-
ted auto-
matically)
S02
Warning
threshold
switching
cycles
Warning
threshold
switching
cycles of
the pilot
valves
0 to
2,147,483,6
00
50,000,000
-
Switching
cycles
warning ra-
tio
Indicator
for valve
wear on
the pilot
valve mod-
ule
0.0 to
100.0%
0.0% (is ad-
justed
automatic-
ally)
P26
Initializa-
tion quant-
ity of calib-
ration
points
Quantity of
calibration
points
when ini-
tializing
1 to 19
9
S09
Operating
time OPEN
Operating
time of the
valve in
open direc-
tion
0.0 to 99.9
s
0.0 s (is ad-
justed
automatic-
ally)
S10
Operating
time
CLOSED
Operating
time of the
valve in
closed dir-
ection
0.0 to 99.9
s
0.0 s (is ad-
justed
automatic-
ally)
P21
Decay time
D-compon-
ent
Decay time
of the D-
component
1 to 5000
ms
100 ms
P22
Differential
component
Amplifying
the D-com-
ponent
0.0 to
100.0
0.0
P23
Propor-
tional amp-
lification
P-amplific-
ation of the
positioner
0.1 to
100.0
1.0 (is ad-
justed
automatic-
ally)
P20
Dead zone Setting the
manual
dead zone
0.1 to
25.0%
1.0%
P44
Dead zone
value auto
Dead zone
value auto
0.1 to 25% 1% (is ad-
justed
automatic-
ally)
P24
Dead
zones func-
tion
Automatic
dead zone
adjustment
manual,
auto
manual
Number
Parameter Description Settings
Initial set-
ting
Set value,
manual
Current set
value for
manual op-
eration
0.0 to
100.0%
-
S06(.1)
Set value
Compar-
ison of set
value and
valve posi-
tion
0.0 to
100.0%
-
S06(.2)
Valve posi-
tion
Compar-
ison of ac-
tual value
and valve
position
0.0 to
100.0%
-
-
I set value
input
Current tar-
get value
signal
0.0 to 22.0
mA
-
-
I actual
value out-
put
Signal ana-
logue out-
put
0.0 to 22.0
mA
-
-
Position
control de-
viation
Control de-
viation for
positioner
-100.0 to
100.0%
-
S05(.1)
Absolute
position
init.
(CLOSED)
Valve abso-
lute posi-
tion end
positions
0.0 to
100.0%
- (is adjus-
ted auto-
matically)
S05(.2)
Absolute
position
init. (open)
Valve abso-
lute posi-
tion end
positions
0.0 to
100.0%
- (is adjus-
ted auto-
matically)
-
Current ab-
solute posi-
tion
Current ab-
solute posi-
tion of the
travel
sensor
0.0 to
100.0%
-
P43
Travel
sensor dir-
ection of
action
Direction of
action of
the travel
sensor
rise, fall
rise
P33
Analogue
output min
Valve posi-
tion at out-
put signal
of 4 mA
0 to 100% 0%
P34
Analogue
output max
Valve posi-
tion at out-
put signal
of 20 mA
0 to 100% 100%
P16
Set value
limit
CLOSED
Lower
range of
the set
value limit
0 to 100% 0%
14 Parameter list