Operating mode: Emergency manual operation
To replace the battery, it may be necessary to move the curtain away from the upper end
position. If the electronics are in another mode such as „All system functions OK“, the drive can
be switched to the emergency manual operation.
I
Please note: A pause of at least 5 seconds must be observed between
the driving movements.
After that the drive can only be moved downwards and the battery can be replaced. To end the
emergency manual operation, the limit switch must be pressed briefly twice.
Operating mode: Mains voltage failure
In the event of a power failure, the status indicator flashes red, but the system remains ready
for operation. Only when the critical battery capacity is reached the drive automatically moves
the blind to the upper end position and remains there. After the mains power failure has been
rectified, the battery can be recharged. The system cannot be put back into operation until the
charge level exceeds the critical battery capacity (>50% capacity).
The red LED flashes.
Operating mode: Critical battery status
If the charge level is <50% the system runs automatically in the upper end position and remains
there. The system only operates again when the charge level is > 50% or after replacement of
the battery.
Yellow and red LEDs flash.
Operating mode: Deep discharge state
If the battery charge drops below the critical battery capacity, the drive retracts the curtain in the
upper end position and then a bit downwards so that the battery can be replaced.
Yellow and red LEDs flash alternately.
Operating mode: Minimum operating temperature not reached
If the operating temperature falls below the minimum permissible operating temperature, the
system runs automatically to the upper end position and the blind remains there. The system
can only operate again when the ambient temperature is above the minimum operating
temperature again.
The yellow LED lights up permanently and the red LED flashes.
External triggering by fire alarm (potential-free contact)
Via the potential-free contact (input - fire alarm) the fire control centre gives the triggering
command (fire alarm signal). The drive then moves independently to the upper end position
and remains there until the release command (fire alarm signal) is switched off. During this
time, the blind cannot be moved.
To move the blind back to the lower end position, the mains voltage must be applied.
Green/yellow and red LEDs flash.
Operation in general:
Operation via a locked control switch. Move via the corresponding key as long as this is
actuated and no end position has been reached or overload occurs in this direction.
Special feature on UP travel, the stop switch stops the travel immediately as long as it is
activated.
Operation:
UP = UP key
DOWN = DOWN key
AS = stop switch
SET = Prog or AS + DOWN
5 sec
1 sec
5 sec
1 sec
5 sec
1 sec
1 sec
break
UP
–
–
–
–
–
–
break
DOWN
break
5 sec
–
break
5 sec
–
break
UP
UP