HART Communicator Fast Key Sequences
The Hart Communicator Fast Key sequences are reported in the following table. Please consider Fast Keys as
shortcuts to rapidly moving through the menu tree.
HART Communicator Fast Key Sequences
Function
Fast Key Sequence
Read PV Pressure 1, 1, 1
Read % of Full Scale 1, 1, 2
Read Analog Output 1, 1, 3
Read SV Electronics Temperature 1, 1, 4
Read TV Snout Temperature 1, 1, 5
Read Peak Pressure Value 1, 2, 1, 3
Read Peak Temperature Value 1, 2, 1, 2
Read Sensor Diagnostic Status 1, 2, 1, 1
Read PV Minimum Span 1, 3, 4
Perform Sensor Self-Test 1, 2, 2
Perform Sensor Master Reset 1, 2, 3
Perform Loop Test 1, 2, 5
Perform D/A Trim 1, 2, 6, 2
Perform Autozero 1, 2, 6, 3, 1
Reset Autozero
1, 2, 6, 3, 2
Perform Device variable trim 1, 2, 6, 3, 3
Device variable trim reset
1, 2, 6, 4
Set Rcal 1, 2, 6, 5
Set Tag 1, 3, 1
Set Long Tag 1, 3, 2
Set PV Unit 1, 3, 3
Set Lower Range Value (LRV) 1, 3, 4, 5
Set Upper Range Value (URV) 1, 3, 4, 4
Display Lower Set Limit (LSL) 1, 3, 4, 1
Display Upper Set Limit (USL) 1, 3, 4, 2
Set Date 1, 3, 5, 1
Set Descriptor 1, 3, 5, 2
Set Message 1, 3, 5, 3
Set PV Dampening 1, 3, 6
Set PV Analog Output Alarm Type 1, 4, 2, 2, 2
Set Poll Address 1, 4, 2, 3, 1
Set Burst Configuration 1, 4, 2, 3, 4
Alarm and Saturation values burst mode
No special requirements are defined for the burst mode.
Alarm and Saturation values in multidrop mode
If the device is in multidrop mode, the NAMUR levels are no longer achievable. Instead thefail safe condition
is indicated by the field device status and by the additional diagnostics.