gefran GTS-T 10 Series Technical Data Manual Download Page 2

I

2

t for blowout: 

450A

2

s

dV/dt critical with output deactivated:
1000V/µs

GTS 25 (SCR version)
Rated current: 25 A@40°C in
continuous service
Non-repetitive overcurrent t=20 ms:
400A
I

2

t for blowout: 

645A

2

s

dV/dt critical with output deactivated:
1000V/µs

GTS 40 (SCR version)
Rated current: 40 A@40°C in
continuous service
Non-repetitive overcurrent t=20 ms:
600A
I

2

t for blowout: 

1010A

2

s

dV/dt critical with output deactivated:
1000 V/µs

GTS 50 (SCR version)
Rated current: 50 A@ 40°C in
continuous service
Non-repetitive overcurrent t=20 ms:
1150A
I

2

t for blowout: 

6600A

2

s

dV/dt critical with output deactivated:
1000V/µs

GTS 60 (SCR version)
Rated current: 60 A@ 40°C in
continuous service
Non-repetitive overcurrent t=20 ms:
1150A
I

2

t for blowout: 

6600A

2

s

dV/dt critical with output deactivated:
1000V/µs

GTS 75 (SCR version)
Rated current: 75 A@ 40°C in
continuous service
Non-repetitive overcurrent t=20 ms:
1300A
I

2

t for blowout: 

8000A

2

s

dV/dt critical with output deactivated:
1000V/µs

GTS 90 (SCR version)
Rated current: 90A@ 40°C in
continuous service
Non-repetitive overcurrent t=20 ms:
1500A
I

2

t for blowout:

11200A

2

s

dV/dt critical with output deactivated:
1000V/µs

GTS 120 (SCR version)
Rated current: 120A@ 40°C in
continuous service (complete with fan
and standard thermostat)
Non-repetitive overcurrent t=20 ms:
1500A
I

2

t for blowout: 

11200A

2

s

dV/dt critical with output deactivated:
1000V/µS

Isolation
Rated isolation voltage 
input/output:
2500VAC rms TRIAC version
4000VAC rms SCR version

Ambient conditions

• Working temperature

da 0 a 80°C  (according to 
dissipation curves)

• Max. relative humidity

50% at 40°C

• Max. installation altitude:

2000m asl

• Pollution level : 3

• Storage temperature: -20..+85°C

Installation notes

Use the high-speed fuse specified 
in the catalog according to the
connection example given.
- Applications with solid state power
units must also include an automatic
safety switch to cut out the load
power line.
For maximum reliability, it is essential
to install the device correctly in the
panel in order to have adequate heat
exchange between the sink and the
surrounding air by natural
convection.
Install the device vertically (max. 10°
inclination to vertical axis)

• Vertical distance between a device
and panel wall  >100mm
• Horizontal distance between a
device and panel wall: at least 20mm
• Vertical distance between one
device and another: at least 300mm.
• Horizontal distance between one
device and another: at least 20mm.

Make sure that the cable channels 
do not reduce such distances; if so,
install the groups cantilevered to the
panel so that air can flow
vertically on the heat sink 
without obstructions.

Limits of use

• dissipation of thermal power of
device with restrictions on
temperature of installation site.

• requires exchange with outside air 
or an air conditioner to transfer
dissipated power outside the panel.
• installation restrictions (distances
between devices to guarantee
dissipation by natural convection)
• max. voltage limits and derivative
of transients in line, for which the 
solid state unit has internal protection
devices (depending on model).
• presence of dispersion current

< 3mA for SCR version GTSs and
< 4mA 4mA for Triac version GTSs.

(max. value with rated voltage
and junction temperature of 125°C).

Summary of Contents for GTS-T 10 Series

Page 1: ...2V Max reverse voltage 36Vdc GTS T10 T20 T25 TRIAC version Control voltage 5 32Vdc Activation voltage 4 2Vdc Deactivation voltage 2Vdc GTS 15 120A versione SCR Control voltage 6 32Vdc Activation volta...

Page 2: ...temperature da 0 a 80 C according to dissipation curves Max relative humidity 50 at 40 C Max installation altitude 2000m asl Pollution level 3 Storage temperature 20 85 C Installation notes Use the h...

Page 3: ...27 mm 108 mm 100 mm 14 mm 18 mm 50 mm max Depth 142 mm Weight GTS 75 90 1300 g Weight GTS 120 1700 g Depth 142 mm Weight 900 g Depth 142 mm Weight 540 g Depth 107 mm Weight 320 g The ON LED is red dur...

Page 4: ...ON OFF Control GTS 60A 480 Vac AC1 50 60 Hz ON AL Load Line 6 32Vcc ON OFF Control GTS 60A 480 Vac AC1 50 60 Hz ON AL R R R R R R Load Line AC1 50 60 Hz GTS 60A 480 Vac ON OFF Control 6 32Vcc AL ON Lo...

Page 5: ...mm2 M6 3 5 6 Nm 9x12 6mm2 M5 1 3 1 8 Nm 9x12 6mm2 M5 1 3 1 8 Nm 11 5x12 16mm2 M5 1 5 2 2 Nm 14x16 50mm2 M5 1 8 2 5Nm 14x16 50mm2 M5 1 8 2 5 Nm 14x16 50mm2 M5 1 8 2 5 Nm Contact Type of pre Max section...

Page 6: ...d voltage 230 230Vac GTS T 230 Version with TRIAC Rated current 15 15Aac 25Aac 40Aac 60Aac 90Aac 25 40 60 90 120Aac 120 Rated voltage 230 230Vac Model GTS GTS Version with double SCR Please contact GE...

Page 7: ...s and heat sources respect the installation distances between one device and another to allow for dissipation of generated heat to keep air in movement we advise you to install a fan near the GTS grou...

Reviews: