OUTPUTS
Allocation of reference signals
40
rL.
R/W
Allocation of reference signal
for alarm relay output
0
Table of reference signals
2
bit
STATE SSR output
OFF = Output off
ON = Output on
R
3
bit
STATE rL output
OFF = Output off
ON = Output on
R
119
R
State of outputs MASKOUT
Table of output states
Read state
bit
0
State SSR output
1
State rL output
+32 For denied logical level in output
50
LD.1
R/W
Function RUN led
51
LD.2
R/W
Function STATUS led
16
Table of function Leds
Function
0
RUN
1
AUTO/MAN
2
ON/OFF software
7
Serial dialog active
9
Softstart Ramp running
1
+16 LED Blinking when active
The state of the LEDs matches the corresponding parameter, except in the following special cases:
- LED 1 (green) + LED 2 (yellow) both flashing rapidly: autobaud in progress
- LED 2 (yellow) flashing rapidly: SSR temperature sensor broken or SSR Over Heat or Rotation Error
or Fuse_open (GTF 150...250A for models with SCR) or Load_short_protection (GTF-Xtra)
or Short_Circuit_Current or Line-Load Terminals Over Heat (GTF 150...250A)
0
Output disabled
1
AL.HB or Power Fault
2
AL.HB
3
Power Fault
4
AL.HB or Power Fault or Fuse Open
5
AL.HB or Fuse Open
6
Power Fault or Fuse Open
7
Fuse Open
8
Communication failure
9
AL.HB or Power Fault or Communication failure
10
AL.HB or Communication failure
11
Power Fault or Communication failure
12
AL.HB or Power Fault or Fuse open or Communication failure
13
AL.HB or Fuse open or Communication failure
14
Power Fault or Fuse open or Communication failure
15
Fuse open or Communication failure