gefran 40T 48 Installation And Operation Manual Download Page 6

 

Pr

Ln

0.0.

3.2.

3.3.

3.4.

3.5.

u(.

(.L.

(.x.

• User calibration

.......

• Custom linearization

• Protection

Protection 

code

 Value        Displayed              Modifiable

               parameters           parameters

  0 

o.1, o.2, o.3, o.4  o.1, o.2, o.3, o.4

  1 

o.1, o.2 

o.1, o.2

 2 

o.1 

o.1

 3 

o.1 

none

+4 to disable In and Ou pages

+8 to disable CF and Sr pages

+16 to enable maintenance of reset latch at power-off (for linear inputs only)

+32 base configuration (the following parameters will not be displayed):

 In

: F.t, F.d, oF., L.L, H.L

 Ou

: On [forced to no. outputs present], rE)

 

F.t, F.d, oF., remain at set value

 

L.L, H.L are forced to L.S, H.S

+64 Management of virtual instrument

+128 Disabilitazione of all the menu except PA (Password) 

Custom linearization 

of main input

Step 0

(beginning of scale 

value)

Display limits 

(-1999...9999)

Step 32

(full scale value)

Display limits 

 (-1999...9999)

Step 33

mV beginning of 

scale

Step 34

mV full scale

Step 35

mV at 50°C

(*)

(*)

(*)

(*) sonly for CPU, TC_LIN e tP = TC CUSTOM

U.C.    CPU T function 

 1       analog retransmission output

 2       Custom RTD sensor

 3       Custom PTC sensor

 4       Custom NTC sensor

 5       Potentiometer (0 to 1V)

Calibration of 

minimum (*)

Calibration of 

maximum (*)

(*) when U.C. = 1 press keys 

Δ

 

∇ 

to 

calibrate analog output

the step value corresponds to input::

mV beginning scale  + n * 

Δ

mV

Δ

mV = (mV full scale - mV beginning scale) / 32

The input value and alarms remain “frozen” for the interval in which the logic input is active.

With the input active, a reset of the alarm memory provokes de-energizing of all the energized relays and resetting of the 

memory of all the alarms.

Input value is sampled; state of alarms is not transferred to outputs; outputs are “frozen”.

When the logic input is active the input value is “frozen” and the outputs are updated according to the calculated alarms 

state, including the ones latched.

• HOLD function

• FLASH function

6

81642H_MHW_40T48_11-2013_ENG

                             6 / 18

Summary of Contents for 40T 48

Page 1: ...ne resistance PTC Type NTC Type Max non linearity error C F selection Linear scale ranges Logic input Function of logic input Alarms Trip points Alarm masking Relay contacyt Logic output Triac output...

Page 2: ...t100 PTC NTC Device structure 3 1 2 Pt100 3 wire PTC NTC Pt100 2 wire Available thermocouples J K R S T B E N L U G D C Respect polarities For extensions use compensated cable appropriate for thermoco...

Page 3: ...eters 999 999 scale points 999 999 scale points Hysteresis for alarm output 3 Pressed for approx 2 sec Keep the F key pressed to browse the menus Release the F key to enter the displayed menu Press th...

Page 4: ...0 C 200 600 199 9 600 0 31 JPT100 F 328 1112 199 9 999 9 Probe PTC NTC 32 PTC C 55 120 55 0 120 0 33 PTC F 67 248 67 0 248 0 34 NTC C 10 70 10 0 70 0 35 NTC F 14 158 14 0 158 0 In case of custom linea...

Page 5: ...points Digital filter on main input Digital filter on process variable display 0 0 20 0 sec 0 0 9 9 scale points TC LIN input parameters 4 to disable digital filter F t average of the last eight value...

Page 6: ...tep 33 mV beginning of scale Step 34 mV full scale Step 35 mV at 50 C sonly for CPU TC_LIN e tP TC CUSTOM U C CPU T function 1 analog retransmission output 2 Custom RTD sensor 3 Custom PTC sensor 4 Cu...

Page 7: ...t 0 For AL2 symmetrical deviation alarm H2 2 t 6 time AL1 AL2 AL1 alarm 1 alarm 2 AL1 AL2 AL1 alarm 1 alarm 2 time AL1 AL2 H2 Normal deviation alarm AL1 absolute AL2 deviation Symmetrical deviation a...

Page 8: ...relays contactors solenoid valves etc if the voltage waveform is strongly distorted by thyristor switching units or by electric motors it is recommended that an isolation transformer be used only for...

Page 9: ...unzione di uscita prevista come OUT2 nello strumento 40T48 Adatta a pilotare carichi in ac sino ad un massimo di 240Vac 1A La schedina automaticamente riconosciuta dallo strumento che abilita visibili...

Page 10: ...rta la funzione di uscita prevista come OUT2 nello strumento 40T48 Adatta a pilotare carichi resistivi sino ad un massimo di 5A a 250Vac 30Vdc La schedina automaticamente riconosciuta dallo strumento...

Page 11: ...orta la funzione di uscita prevista come OUT3 nello strumento 40T48 Adatta a pilotare carichi resistivi sino ad un massimo di 5A a 250Vac 30Vdc La schedina automaticamente riconosciuta dallo strumento...

Page 12: ...ie Karte automatisch und aktiviert die Funktionen f r die Anzeige und die Einstellung der entsprechenden Parameter GENERALITES Cette carte supporte la fonction entr e logique en tant qu alternative OU...

Page 13: ...ri relativi PROFILE This board supports the output function provided as OUT3 on the 40T48 instrument Suitable for piloting logic inputs typical application for interface to solid state switches GTS Th...

Page 14: ...tri relativi PROFILE This board supports the output function provided as OUT2 on the 40T48 instrument Suitable for piloting logic inputs typical application for interface to solid state switches GTS T...

Page 15: ...Si se desea obtener mayor precisi n se deber efectuar la cali braci n usuario salida anal gica procediendo de la manera ilustrada en el manual de uso Tipo de salida Jumper S1 20mA OFF abierto est nda...

Page 16: ...cheda supporta la funzione di uscita prevista come OUT4 nello strumento 40T48 Adatta a pilotare carichi resistivi sino ad un massimo di 5A a 250Vac 30Vdc La schedina automaticamente riconosciuta dallo...

Page 17: ...MODBUS USCITA SERIALE OUT4 SERIAL OUTPUT OUT4 SERIELLER AUSGANG OUT4 SORTIE SERIE OUT4 SALIDA SERIE OUT4 SA DA SERIAL OUT4 PROFILO Questa scheda supporta la funzione di uscita prevista come OUT4 nello...

Page 18: ...Gefran 40T 48 Installation Manual Temperature Indicator Alarm www thermon co za CPT 27 21 762 8995 JHB 27 11 966 9800 Powered by TCPDF www tcpdf org...

Reviews: