(.I.
F.t
f.d
d.P.
l.s
x.S
oF.
d.1.
t.U.
t.d.
L.L
x.L
0v
0.n
1.t
2.t
3.t
4.t
f.0
r.a
t.M
1
re
0 None
1 Zero
2 Hold
3 Flash
4 Max. peak display
5 Min. peak display
6 Delta peak display
7 Peak memory reset
8 Zero + peak memory reset
9 Alarms reset
10 Peak + alarms reset
11 Zero + alarms reset
12 Peak + zero + alarms reset
13 Output status OUT1
14 Output status OUT2
15 Output status OUT3
16 Output status OUT4
17 Blocked keyboard (only
d.1.
)
18 Potentiometer Calibration
(only
t.U.
and
t.d.
)
19 OFFSET (only
t.U.
and
t.d.
)
d.I. - t. u. - t. d.
min…max scale
of input selected
in t.P
Decimal point
position for main
input scale
Minimum limit of
main input scale
and analogue output
Maximum limit of
main input scale
and analogue output
Offset correction
of main input
Select
function of
digital input
High limit for
the alarms set point
-999...999
scale points
dP
Format
0
XXXX
1
XXX.X
2 *
XX.XX
3 *
X.XXX
min…max scale
of input selected
in t.P
L.S ... H.S
Raise key
function
active only in
P.V.selection
Low limit for the
alarms set point
L.S ... H.S
+4 to display Lo below value LS-(HS-LS)/256 (non-
custom linear inputs only)
(*) not available for scales TC, RTD, PTC, NTC
Lower key
function
active only in
P.V.selection
Select sampling
time (resolution).
For linear input
0...1V/POT only.
0 120ms > 14bits 16000 points
1 60ms
> 14bits 16000 points
2 30ms
> 13bits 8000 points
3 15ms
> 12bits 4000 points
Digital filter
on main input
Digital filter on
process variable
display
0.0...20.0 sec
0.0...9.9
scale points
• TC / LIN input parameters
+4 to disable digital filter F.t (average
of the last eight values sampled)
• Output parameters
Valore Direct Absolute or Normal or
(high limit) Relative Symmetric
Inverse to previous (window)
(low limit) absolute
0
Direct
Absolute Normal
1
Inverse Absolute Normal
2
Direct
Relative
Normal
3
Inverse
Relative
Normal
4
Direct
Absolute Symmetric
5
Inverse Absolute Symmetric
6
Direct
Relative Symmetric
7
Inverse
Relative Symmetric
Output settings
Number of outputs
Alarm type 1
(absolute only)
0 ... 4
1. t - 2. t - 3. t - 4.t
Alarm type 2
Alarm type 3
Delay for F.O.
0 ... 99 min
or sec
+8 to disable on power-up until first
alarm
+16 to memorize
+32 to filter with F.O. mode (output filter
mode)
Minimum
output pulse
0 ... 99 sec
Disabled by setting value 0
Displayed if associated with at least
one output
Fault action
(in case of
damaged
sensor)
Er, br.
Value OUT 1 OUT 2 OUT 3 OUT 4
0
OFF
OFF
OFF
OFF
1
ON
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
3
ON
ON
OFF
OFF
4
OFF
OFF
ON
OFF
5
ON
OFF
ON
OFF
6
OFF
ON
ON
OFF
7
ON
ON
ON
OFF
8
OFF
OFF
OFF
ON
9
ON
OFF
OFF
ON
10
OFF
ON
OFF
ON
11
ON
ON
OFF
ON
12
OFF
OFF
ON
ON
13
ON
OFF
ON
ON
14
OFF
ON
ON
ON
15
ON
ON
ON
ON
Output filter mode
+ 8 time base max. 99 min
(default = 99 sec)
0 not active: calculated status
is sent directly to relay
1 On delay (DON)
2 On delay after it has
been turned off (DBI)
3 Off delay (DOF)
4 Delay for activation only
at power-up (DPO)
Alarm type
4
5