GH10HA USER MANUAL
PAGE
5
Issue I
APRIL 2013
3.
TECHNICAL DATA
Power supply
230V AC +10% -15%
NTC sensor resistance
characteristics
PT1000 sensor
resistance
characteristics
Operating temperature
range
+5
°
C to +40
°
C
Humidity
20% to 80% RH
Temp.
°C
Resistance
Ω
Temp.
°C
Resistance
Ω
Fan protection
2A
0
7174,89
0
1000,00
Sensors type
NTC 2,2kΩ, PT1000
10
4374,83
50
1194,00
Sensors operating
temperature range
NTC:
0
°
C÷100
°
C
20
2747,10
100
1385,10
PT1000: 0
°
C÷400
°
C
30
1774,91
150
1573,30
40
1172,09
200
1758,60
50
795,08
250
1941,00
Output
Maximum
continuous load
60
547,95
300
2120,50
70
384,62
350
2297,20
HUW pump / mix pump
1A
200W
80
275,86
400
2470,90
CH pump
1A
200W
90
202,37
450
2641,80
Fan*
1A
200W
100
149,16
500
2809,80
550
2974,90
600
3137,10
*If an auxillary or relay proxy is connected, a circuit breaker dedicated to
this (eg, a varistor) must be used. Failure to do so may result in controller
output malfunction or damage.
4.
ELECTRICAL SYSTEM AND CONNECTION RULES
1.
The boiler room should be equipped with a 230V/50Hz electrical system, according to the
applicable regulations.
2.
The electrical system (regardless of its type) should be terminated with a connection outlet fitted
with a protective terminal.
Use of an outlet without a protective terminal causes electrical shock
hazard!!!
3.
Connect the Controller to a separately installed power line protected with a properly selected
quick circuit-breaker or a residual-current device (RCD breaker).
Do not connect any other devices
to this line!!!
THE CONTROLLER IS POWERED FROM 230V/50HZ MAINS
ANY REPAIRS MAY BE CARRIED OUT ONLY WITH POWER SUPPLY
CUT OFF AT THE FUSE
Summary of Contents for GH10HA