GA03HA-01
User Manual
PPUH „GECO” Sp. z o.o.
Page
9 Edition I
Valid from 2017-07-26
If the boiler controller is connected correctly to the GA03HA-01 room panel, this will be detected
automatically by the controller and activation does not require any additional steps or settings from the user.
Once connected, the boiler controller operates according to the room panel settings. Disconnection or
damage to the cable connecting the panel and the controller will result in the light behind the icon
on the room panel, as well as the loss of the icons
on the controller main screen when the power is
disconnected for 15 seconds.
5.
„Quick start” Function
When the room panel is connected to the boiler controller, the device is ready for use. In order to use
„Quick start” for the GA03HA-01 room panel, follow the steps below:
1.
Connect equipment to the boiler controller (
⇒
section 4, page 8)
⇒
2.
Switch on using the button
. The following screen will appear:
Tabela 1. Room panel factory settings
Description
Range
Factory setting
Daytime temperature (comfort)
7
0
C - 30
0
C
21
0
C
Night time temperature (economy)
7
0
C - 30
0
C
17
0
C
Daily settings
1 - 9
Programme 3
Weekly settings
Monday-Sunday
Programme 2
6.
Operating GA03HA-01