III. Dropmaster Operating Procedures
1.
Dropmaster is to be used only by a qualified fire protection technician.
2.
The Dropmaster is designed to be used on one sprinkler system at a time.
3.
Utilize normal shut down procedures for ‘Alarms’; i.e. customer/owner must notify
service monitoring alarms and insurance company.
4.
Drain system main and inspector’s test at main location and at auxiliary drains.
Research
system as to size and amount of sprinkler lines, sprinkler heads and what length the
drops are. To determine the distance from Dropmaster to the area being serviced, a
preliminary calculation should be done to determine amount of water trapped in
system. See page 6 for water calculations.
5.
Close all control valves on the sprinkler system on which you will be working drain as
much water as possible at the main drain and the inspectors test valve or auxiliary drain
valves before hooking up the Dropmaster to the sprinkler system.
6.
Check to see if the fire department connection and ball drips are on system side of alarm
valve. If they are on system side of alarm valve they must be capped or plugged before
you begin using the Dropmaster.
7.
IMPORTANT
- Before connecting Dropmaster, you must review the power sources. The
Mini E unit requires a 120 volt 15 amp circuit with no extension cords.
8.
Connect the ‘Dropmaster Odor and Water Eliminator’ to the main drain or any
convenient drain connection. When putting the Dropmaster in to service according to
specified procedures, it will maintain a constant 10.00 inches of mercury vacuum
pressure, which in turn will cause a siphon effect when a sprinkler head is removed; thus
allowing the sprinkler fitter the time required to replace the sprinkler head with no water
back splash or odor from the pipe.
9.
Connect the 1” discharge hose to the drains, any outlet.
10.
Turn on the unit, ensure the unit is operating and pulling a vacuum on the system to be
worked on.
-4-
Summary of Contents for DROPMASTER Mini E
Page 1: ...OPERATION MANUAL...
Page 11: ......