background image

DIS. 0534014   COD. 27101443 Istruzione / User’s Manual  Pag.1/4

  

 

 

   Sensore gas per centrali termiche 

   Remote gas sensor for heating plants 

 

 

GECA Srl  Via E. Fermi 98 -25064 Gussago (Brescia) Italy http://www.gecasrl.it  Tel:+39 030/3730218 Fax:+39 030/3730228

 

 

 

 

                        

 
 
 

GAS 

SENSOR

IP44

 

 

 

 

 
 
 

 
 
 
 
 

 
 
 

 

Caratteristiche tecniche / 

Technical specifications

 

 

Alimentazione / 

Power supply

 

12Vdc (-10/+15%) - 165mA (1,98 W) 

Uscita / 

Output

  

4÷20mA Lineare / 

Linear

  

Resistenza di carico / 

Load resistor

  

100 

 max 

Campo di misura / 

Standard range

  

0 ÷ 20 % LIE / LEL 

Sensore / S

ensor 

 

Catalitico / 

Catalytic 

 

Tempo di risposta T

50 

 / 

Response time

 T

50

  

< 30 secondi / 

seconds

  

Precisione / 

Accuracy

  

± 10 % 

Deriva a lungo termine in aria pulita / 

Long time drift in pure air

  

<±5 % LIE anno / LEL 

year

  

Vita media in aria pulita / 

Expected life in pure air 

 

10 anni / 

years

  

Temp./umidità di funzionamento / 

Operation Temp./Humidity 

 

-10 ÷ +50 °C / 5÷90 % r.h. 40°C 

Temp./umidità di immagazzinamento / 

Storage Temp./Humidity 

 

-25 ÷ +55°C / 5÷95 % r.h. 

Grado protezione / Rating  

IP44 

Dimensioni / 

Size 

 

110 x 75 x 70 mm 

 

DESCRIZIONE 

I modelli della serie ST441 sono sensori 4÷20mA lineari a 
tre fili in grado di rilevare gas combustibili ed utilizzano sen-
sori di tipo catalitico tarabili al 20% LIE per alcuni gas. 
L'apparecchio è costituito da una custodia che contiene il 
circuito elettronico e i morsetti di collegamento; il sensore è 
inserito all'interno del portasensore, posto su coperchio della 
custodia. 
Gli ST441 vengono normalmente collegati alle nostre cen-
trali di rilevazione gas per centrali termiche come indicato 
sopra in Tabella. 

FUNZIONAMENTO 

Il sensore catalitico è praticamente insensibile alle variazioni 
di umidità e temperatura, è in grado di rilevare gas infiam-
mabili e la taratura viene eseguita per il gas che il sensore 
deve rilevare.  
Per questo può rilevare anche altri gas o solventi infiamma-
bili se sono presenti nello stesso locale.  
Il sensore, quando viene alimentato, necessita di un tempo 
di preriscaldo di circa 30 secondi. Dopo questo tempo è in 
grado di rilevare il gas, ma raggiunge le condizioni di stabilità 
ottimali dopo circa 3 ore di funzionamento continuo. 
Dopo questo tempo si consiglia di effettuare una verifica in 
aria pulita del “4mA” e,  solo se necessario, procedere alla 

Regolazione del 4mA

” come indicato a pag. 3, per adattare 

il sensore alle condizioni ambientali. 

 

GENERAL INFORMATION 

The models series ST441, is a three-wire 4÷20mA linear 
sensores able to detect combustible gases employing a 
catalytic sensor calibrated up to 20% LEL to different gases. 
The instrument comprises of a thermoplastic terminal box 
which contains the electronic circuit, the connecting termi-
nals and the sensor placed in its housing on the cover. 
The ST441 are normally connected to the GECA gas de-
tecting central systems for heating plants, as shown in the 
Table above. 

OPERATIONAL DESCRIPTION 

The catalytic sensor is practically insensitive to humidity and 
temperature variations. The sensor being designed to detect 
flammable gases and the calibration is carried out with the 
specific gas to be detected. Anyway, it can contemporane-
ously detect any other flammable gas that should be present 
in the same environment. 
When powered, the sensor needs a time of preliminary 
heating of about 30 seconds. 
After this period, the sensor is able to detect gas even if it 
attains the optimum stability conditions after about 3 hours 
continual functioning. Therefore, after that time we advise to 
check in clean air the “4mA” output.  
If is necessary “

4mA calibration

” can be carried out as ex-

plained on page 3.This calibration is necessary to adjust the 
sensor to the environment conditions. 

 

Centraline collegabili a ST441G e ST441M 

Detectors which can be connected to the ST441G – ST441M 

 

Modello 

Model  

N°Sensori 

Sensors number  

CTM31 – CTM21 – CTM11 

CTP31 – CTP21 

1 ÷ 3 

Summary of Contents for CTM31

Page 1: ... infiamma bili se sono presenti nello stesso locale Il sensore quando viene alimentato necessita di un tempo di preriscaldo di circa 30 secondi Dopo questo tempo è in grado di rilevare il gas ma raggiunge le condizioni di stabilità ottimali dopo circa 3 ore di funzionamento continuo Dopo questo tempo si consiglia di effettuare una verifica in aria pulita del 4mA e solo se necessario procedere alla...

Page 2: ...ro gli Idrocarburi clorurati Trielina o Tetracloruro di car bonio Dopo un breve tempo in aria pulita il sensore riprende il proprio funzionamento normale Importante il sensore utilizzato di tipo catalitico funziona solo in presenza di Ossigeno Faults In case of sensor damage the S output falls down to 0mA FAULT The signal is then indicated as a damage situation All this happens also when an interr...

Page 3: ... trasmetti tore in LIE è 0 3 v v l uscita deve essere m A 16 x 0 29 0 3 4 19 46 Tolleranza 0 5mA Nel caso in cui non si riscontrasse tale valore ruotare il trimmer P2 posto sul circuito stampato fino a leggere il valore richiesto Do not use pure gases or a lighter directly on the sensor since they could damage it irremediably The Models ST441G LPG Model ST441G is able to detect combustible gases u...

Page 4: ...TABELLA A ST441G GPL LPG TABELLA B ST441M Metano Methane Uscita Output ma LIE LEL v v Uscita Output ma LIE LEL v v 4 0 0 4 0 0 8 5 0 075 8 5 0 4 12 10 0 15 12 10 0 5 20 20 0 3 20 20 1 Vdc 4 20mA mA Fig 1 Verifica Test P2 S P1 Centrale rivelazione gas Gas detector RL Fig 2 Tester di calibrazione Calibration Tester 0 3L min Fig 3 Posizionamento Positioning Made in Italy ...