Rectifying malfunctions
Malfunctions during operation are indicated by the control unit displays. The malfunction diagnosis is
completed using the Geberit SetApp. The malfunctions are displayed in the app in the <Messages> menu.
Malfunction
Cause
Rectification
No flush actuation,
green LED off
Operating voltage inter-
rupted
▶ Check the mains voltage.
▶ Check the power supply unit.
No flush actuation,
green LED flashes.
• No flushing
programme active
• Solenoid valve
defective
• Control unit defective
▶ Check flushing programmes with Geberit SetApp.
▶ Test solenoid valve with the <Test> button.
▶ Replace the control unit.
Red LED flashes.
Warning:
e.g. maintenance
interval expired
▶ Read out malfunction message with Geberit SetApp.
▶ Rectify malfunction according to instructions in the
Geberit SetApp.
Red LED and buzzer
on
1)
Malfunction:
e.g. volumetric flow rate
sensor defective
▶ Read out malfunction message with Geberit SetApp.
▶ Rectify malfunction according to instructions in the
Geberit SetApp.
1)
Malfunction message with buzzer only if <Basic settings> are activated in the menu.
18
45035999171656331-1 © 06-2019
966.709.00.0(03)
Summary of Contents for 616.211.00.1
Page 1: ...MAINTENANCE MANUAL INSTANDHALTUNGSANLEITUNG MANUEL D ENTRETIEN ISTRUZIONI PER LA MANUTENZIONE...
Page 105: ...1 2 1 2 45035999171656331 1 06 2019 966 709 00 0 03 105...
Page 106: ...7 6 9 6 56 9 9 2 6 9 7 9 9 9 6 9 3 1 2 3 106 45035999171656331 1 06 2019 966 709 00 0 03...
Page 107: ...4 1 2 9 3 45035999171656331 1 06 2019 966 709 00 0 03 107...
Page 109: ...6 45035999171656331 1 06 2019 966 709 00 0 03 109...
Page 110: ...110 45035999171656331 1 06 2019 966 709 00 0 03...
Page 111: ...45035999171656331 1 06 2019 966 709 00 0 03 111...