background image

20

Before you call for service…

Co

ns

um

er

 S

up

po

rt

Tr

ou

bl

es

ho

ot

in

Ti

ps

Ca

re

 a

nd

 C

le

an

in

g

O

pe

ra

tin

In

st

ru

ct

io

ns

Sa

fe

ty

 In

st

ru

ct

io

ns

troubleshooting tips 

save time and money! Review the charts on the

following pages first and you may not need to call for

service.

Problem

Possible Causes

What To Do

Zoneline does

The unit is 

Make sure the Zoneline plug is pushed completely 

not start

unplugged.

into the outlet.

The power cord is not

Remove the room cabinet and make sure that the 

firmly attached.

yellow connector on the end of the power cord is 

firmly engaged.

The fuse is blown/circuit

Check the house fuse/circuit breaker box and replace

breaker is tripped.

the fuse or reset the breaker.

The unit is waiting for

This is normal. The Zoneline will start again after 

the compressor overload

it resets.

protector to reset.
Power failure.

If power failure occurs, set the mode control to 

STOP.

When power is restored, set the mode control to the 

desired setting.

There is a protective time delay (up to 3 minutes) to 

prevent tripping of the compressor overload. For this 

reason, the unit may not start normal heating or cooling 

for 3 minutes after it is turned back on.

The current interrupter 

Press the 

RESET

button located on the power cord plug 

device is tripped.

or the box near the plug.

If the 

RESET

button will not stay engaged, discontinue use 

of the Zoneline and contact a qualified service technician.

Zoneline does not cool

Indoor airflow 

Make sure there are no curtains, blinds or furniture

or heat as it should

is restricted.

blocking the front of the Zoneline.

Outdoor airflow is

Make sure the rear grille is not restricted. This can 

restricted or recirculated.

cause the unit to cycle off due to the compressor 

overload protector.

Outdoor grille must have a minimum of 65% free area. 

Non-GE grilles may be too restrictive for proper 

performance. Consult your salesperson for assistance.

The temp control may

Turn the control to a lower or higher setting.

not be set properly.

NOTE: 

the temperature limiter may be limiting the 

temperature range.

The air filter is dirty.

Clean the filter at least every 30 days.

See the 

operating instructions

section.

The room may have 

When the Zoneline is first turned on you need to

been hot or cold.

allow time for the room to cool down or warm up.

Outdoor air is 

Set the vent control to the closed position.

entering the room.

Burning odor at the start

Dust is on the surface 

This can cause a “burning” odor at the beginning of

of heating operation

of the heating element.

the heating operation. This odor should quickly fade.

Summary of Contents for AZ61H15DAB

Page 1: ...inet and Case 9 Ventilation Filter 9 Installation Instructions Electrical Connection 13 16 Installing the Zoneline 17 18 Optional Drain Kit 19 Preparation 11 Replacing an Existing Unit 12 Troubleshooting Tips 20 21 Normal Operating Sounds 22 Consumer Support Consumer Support Back Cover Warranty 23 Español For a Spanish version of this manual visit our Website at www zoneline com literature Para co...

Page 2: ...damaged A damaged power supply cord must be replaced with a new power supply cord obtained from the manufacturer and not repaired Do not use a cord that shows cracks or abrasion damage along its length or at either the plug or connector end Unplug or disconnect the Zoneline at the fuse box or circuit breaker before making any repairs NOTE We strongly recommend that any servicing be performed by a ...

Page 3: ...shows the set temperature not the room temperature Sleep Press to set the air conditioner to run for 8 hours before it automatically returns to the previous setting When in the cooling mode and the sleep timer is set the set temperature will automatically increase 2 F after the second hour then 1 F each hour over the next two hours Also the fan speed will change to low When in the heating mode the...

Page 4: ... efficiency Energy Tip Keep the vent control in the closed position The room air will be filtered and circulated Air Direction To change the air direction remove the room cabinet Remove the 7 louver screws that hold the louver insert in place Flip the louver insert 180 replace the screws and the room cabinet Remove the room cabinet and flip the louver insert to change the air direction 4 Other fea...

Page 5: ...he down arrow to set the indoor fan to cycle on off when the unit is heating or cooling Press the up arrow to set the indoor fan to run continuously This is shown in the second digit of the display Press AUX SET to confirm your selection and exit AUX SET mode or press MODE to continue setting other functions 8 Auxiliary Set Button Access Cover Cooling Cycle Heating Cycle Cooling Continuous Heating...

Page 6: ...X SET mode or press MODE to continue setting other functions When Freeze Sentinel is activated it automatically provides heat without user interface This helps to prevent plumbing damage by turning the heater and indoor fan ON at 41ºF and OFF at 46ºF When Heat Sentinel is activated it automatically provides cooling without user interface This helps to prevent an excessively hot room by turning the...

Page 7: ...only Green High Speed Fan Green Low Speed Fan Red 24 V AC only EXT FAN CDC 24 VAC R FAN LO G FAN HI G REV VAL B COMP Y AUX HEAT W COMMON C Duct Mode The default setting for Mode 7 is OFF This setting is used when the unit is installed using a duct adapter kit If the unit is ducted the Duct Mode needs to be set to ON This increases the fan speed to ensure proper circulation Press MODE until a 7 app...

Page 8: ...et to ON for the unit to operate with a Class 2 Remote Wall Thermostat See the installation instructions supplied with the remote thermostat and Mode instructions on page 7 IMPORTANT The Zoneline thermostat connections provide 24 V AConly If using a digital electronic wall thermostat you must set it to the 24 V ACsetting See the Installation Instructions for the wall thermostat CAUTION Damage to a...

Page 9: ...ge the unit Use a vacuum to remove debris from the filter Use a damp rag to wipe down the filter and surrounding area after vacuuming Outdoor Coils The coils on the outdoor side of the Zoneline should be checked regularly If they are clogged with dirt or soot they may be professionally steam cleaned You will need to remove the unit from the wall sleeve to inspect the coils The dirt buildup occurs ...

Page 10: ...hrough the filters from the back side Dry thoroughly before replacing NOTE The air filters are interchangeable and will fit in either the right or left side To remove the air filters To replace the air filters CAUTION Do not operate the Zoneline without the filters in place If a filter becomes torn or damaged it should be replaced immediately Operating without the filters in place or with damaged ...

Page 11: ...rdinances For personal safety this Zoneline must be properly grounded Protective devices fuses or circuit breakers acceptable for Zoneline installations are specified on the nameplate of each unit Do not use an extension cord with this unit Aluminum building wiring may present special problems consult a qualified electrician When the unit is in the OFF position there is still voltage to the electr...

Page 12: ...ctors and gaskets that mount to the unit to direct the hot exhaust air away from the air intake to allow the unit to function properly The grille must have a 65 minimum free area Any vertical deflectors in the existing rear grille should be removed to decrease condenser air recirculation that can cause the unit to short cycle and lead to premature component failure use the correct power cord Local...

Page 13: ... is done in accordance with these instructions and all electrical codes Branch Circuit and Proper GE Unit Amperage Rating Subbase Kit 15 RAK204D15P 20 RAK204D20P 30 RAK204D30P A power supply kit with LCDI must be used to supply power to the Zoneline unit The appropriate kit is determined by the voltage the means of electrical connection and the amperage of the branch circuit Connections of 208 or ...

Page 14: ...r use on 7000 BTUmodels The instructions provided with the selected subbase kit must be carefully followed It is the responsibility of the installer to ensure the connection of components is done in accordance with these instructions and all electrical codes Branch Circuit and Proper GE Power Unit Amperage Rating Subbase Kit Supply Kit 15 RAK204E15 RAK5172 20 RAK204E20 RAK5202 30 RAK204E30 RAK5302...

Page 15: ...unctionbox toattachconduitcomingfromthebranchcircuit Removetheknockout attachtheconduitandbringwires intothejunctionbox Leave6 ofwirefreeattheendof theconduittoallowconnectionstobemade 2 If a fuse and fuseholder are to be used the knockout at the top of the box is for mounting a Buss fuseholder Be sure the fuse and fuseholder are of the same rating as the branch circuit Leadwires at the fuse can b...

Page 16: ...Breaker 4 70 4 53 KW 230 208 Volt Heater Wattage Power Supply Kits Circuit Protective Device 230 208 Volts RAK4157 15 Amp Time Delay Fuse or Breaker 2 40 2 32 KW RAK4207 20 Amp Time Delay Fuse or Breaker 3 30 3 20 KW RAK4307 30 Amp Time Delay Fuse or Breaker 4 70 4 53 KW 265 Volt Heater Wattage Power Supply Kits Circuit Protective Device 265 Volts RAK5157 15 Amp Time Delay Fuse or Breaker 2 40 KW ...

Page 17: ...ases are insulated Insulation kit RAK901L is available for use with RAB77A4 or existing uninsulated wall cases when needed NOTE For installation with a subbase or duct adapter see the instructions packed with those kits 1 Stiffener Protective panel Slit PREPARE THE uNIT Carefully remove shipping tape and foam shipping blocks from the room cabinet compressor and vent door There may be multiple bloc...

Page 18: ... rail along the unit top 1 then pushing it in at the bottom 2 4 Installation Instructions 18 NOTE There are several extra holes in the unit side flanges for installation in wall cases other than GE To avoid damaging the flange insulation the installer should use an awl or other sharp tool to puncture the insulation in the appropriate holes before installing the attachment screws INSTALLINg THE ZON...

Page 19: ...lding walls we recommend the use of RAD10 Drain Kit External Drain See the Installation Instructions in the RAD10 kit Internal Drain See the Installation Instructions in the RAD10 kit Type A screw for metal case or Type B screw for molded case Square drain holes Square drain holes The drain is located under the cabinet Neoprene sponge gasket Steel mounting plate 1 2 O D drain tube Neoprene sponge ...

Page 20: ...nterrupter Press the RESETbutton located on the power cord plug device is tripped or the box near the plug If the RESET button will not stay engaged discontinue use of the Zoneline and contact a qualified service technician Zoneline does not cool Indoor airflow Make sure there are no curtains blinds or furniture or heat as it should is restricted blocking the front of the Zoneline Outdoor airflow ...

Page 21: ...ff the warm enough during produces air that feels heat pump and warms with electric heat only heating operation cooler than desired NOTE use of this option will result in increased energy consumption The unit is not The Smart Fan Auxiliary See smart fan Cooling Heating on page 5 blowing out air Controls may be set to cycle The electric heating The power cord is not Remove the room cabinet and make...

Page 22: ... will run regardless if the unit may be cooling or heating Other times the fan will run longer than the heating cooling cycle or kick on occasionally This is normal and is done to improve room comfort and balance You may notice a few minutes delay in starting if you try to restart the Zoneline too soon after turning it off or if you adjust the thermostat right after the compressor has shut off Thi...

Page 23: ...r due to unreasonable use including failure to provide reasonable and necessary maintenance Failure or damage resulting from corrosion due to installation in a coastal environment except for models treated with special factory applied anti corrosion protection as designated in the model number Damage to product caused by improper power supply voltage accident fire floods or acts of god Incidental ...

Page 24: ...he hearing impaired please call 800 TDD GEAC 800 833 4322 Parts and accessories GEAppliances com Individuals qualified to service their own appliances can have parts or accessories sent directly to their homes VISA MasterCard and Discover cards are accepted Order on line today 24 hours every day or by phone at 800 626 2002 during normal business hours Instructions contained in this manual cover pr...

Reviews: