4.
Tighten the clamps (15) and screws (39) to a torque of 1 Nm (0.7 lbft).
5.
Align the pneumatic and electrical connections in accordance with the valve
block configuration.
6.
Close the air connection Y1 with a sealing plug (23) since the control top
T.VIS A-15 has an inner air duct.
Fig.29
7.
Perform commissioning, see Chapter 6, Page 41 and Chapter 7, Page 67.
®
Done.
6.6.4
Mounting to a Butterfly Valve T-smart 8000
Requirement:
•
Pay attention not to kink the air hoses when mounting the control top.
Carry out the following steps:
1.
Fit the bearing (201) into the locking screw (198).
Fig.30
2.
Fit the O-ring (210).
3.
Use a face spanner to screw the locking screw (198) into the actuator (A.1).
Assembly and installation
Mounting the control top to different valves
430BAL010699EN_6
58
17.03.2022