Technical data: non-cyclical data exchange
Sub-
index
Offset
Function
Access
rights
Range
Default
Signal
0x0B
0x0A
Device ID 2
R/W
0x00 - 0xFF
0x34
0x0C
0x0B
Device ID 3
R/W
0x00 - 0xFF
0x56
Index 0x01 - Parameter
0x01
0x00
Colou Selection
R/W
0x00 - 0x01
0x01
0= yellow
1= green
0x02
0x01
Tolerance
R/W
0x00 - 0x04
0x02
0= 2.0mm
1= 1.0mm
2= 0.7mm
3= 0.3mm
0x03
0x02
Signal Damping
R/W
0x00 - 0x04
0x03
0= 1.0 sec.
1= 0.5 sec.
2= 0.1 sec.
3= OFF
0x04
0x03
LEFF
R/W
0x00 - 0x04
0x02
0= OFF
1= VT-Lift
2= DT-Lift
3= VT + DT-Lift
0x05
0x06
0x04
0x05
Not-Activated
Position
M
0x00 - 0x04
0x00 - 0xFF
0 … 1023 (10Bit)
0 … 78mm
0x07
0x08
0x06
0x07
Activated Position
M
0x00 - 0x04
0x00 - 0xFF
0 … 1023 (10Bit)
0 … 78mm
0x09
0x0A
0x08
0x09
Lift Position
M
0x00 - 0x04
0x00 - 0xFF
0 … 1023 (10Bit)
0 … 78mm
Where access to the entire record of an index takes place, the offset within
the record applies (table above).
On account of the setup of the T.VIS necessary for commissioning and
following seal changeover, we have refrained from implementing data
retention!
5.5
Specifications for AS-interface
Technical data: supply
Designation
Description
Supply voltage UV
26.5...31 V DC
Current consumption
- No-load current
≤ 25 mA
- One solenoid valve
35...45 mA
Total
approx. 90 mA
Software version A and B (see version labels AASi / BASi)
Technical data
Specifications for AS-interface
430BAL010699EN_6
32
17.03.2022
Summary of Contents for T.VIS A-15