Value
Description
Cycle Off Timer
This value displays the remaining time before the compressor will stop automati-
cally. It will only be visible if Automatic Start/Stop is enabled in the configuration.
The value is measured in seconds.
Motor Start to Start Timer
This value displays the remaining time that must elapse after the compressor is
started before it may be safely started again. The value is measured in seconds.
Motor Stop To Start Timer
This value displays the remaining time that must elapse after the compressor is
stopped before it may be safely started again. The value is measured in seconds.
Oil Drain Timer
This value displays the remaining time that the compressor must wait for oil to
drain from the system before the compressor may be safely started. The value is
measured in seconds.
Accumulated Run Time
Hours
This value displays the total amount of time the compressor has run. The value is
measured in hours.
Capacity Percentage
This value displays the current reading of the capacity slide. The value is meas-
ured in percent.
kWh Demand
This value displays the currently estimated kWh demand of the compressor. The
value is measured in kWh.
3.7.3
Digital Inputs/ Outputs
Hint!
The assignment of the data points is dependent on the configuration. Check the electrical con-
nection diagram to identify the exact layout of the data points.
Value
Description
Emergency Stop
This input monitors the status of the Emergency Stop switch. It will be energized
for normal panel operation. If this input ever becomes de-energized, an Emer-
gency Stop shutdown will be triggered. The states are
On
or
Off
.
Compressor Interlock
This input monitors the status of the compressor run feedback module. It will be
energized while the compressor is running, and de-energized while the compres-
sor is stopped. If this input ever becomes de-energized while the compressor is
running, or energized while the compressor is stopped, an interlock alarm condi-
tion will be triggered. The states are
On
or
Off
.
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Operating Data
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
179