5
Safety Instructions
Operating Instructions
Care and Cleaning
Troubleshooting T
ips
Consumer Support
GEAppliances.com
Temperature Limiting
(Requires room air sensor kit–RAVRMS)
Temperature limiting can reduce energy costs
by limiting the lowest temperature that can be
set for cooling and the highest temperature that
can be set for heating. Temperature limiting is
controlled by switches 1–6 on the top block
of auxiliary controls. The first three switches are
used to select the cooling limits. The next three
switches are used to control the heating limits.
Temperature limiting during COOL mode
(all temperatures shown in °F)
UP
DOWN
Minimum
Maximum
NONE
1, 2, 3
60°
85°
1
2, 3
64°
85°
1, 2
3
66°
85°
2
1, 3
68°
85°
2,3
1
70°
85°
1, 2, 3
NONE
72°
85°
1, 3
2
74°
85°
3
1, 2
76°
85°
Temperature limiting during HEAT mode
(all temperatures shown in °F)
UP
DOWN
Minimum
Maximum
NONE
4, 5, 6
60°
85°
4
5, 6
60°
80°
4, 5
6
60°
78°
5
4, 6
60°
76°
5,6
4
60°
74°
4, 5, 6
NONE
60°
72°
4, 6
5
60°
70°
6
4, 5
60°
65°
TL1 (C) (Temp. Limit 1–Cool)
TL2 (C) (Temp. Limit 2–Cool)
TL3 (C) (Temp. Limit 3–Cool)
TL1 (H) (Temp. Limit 1–Heat)
TL2 (H) (Temp. Limit 2–Heat)
TL3 (H) (Temp. Limit 3–Heat)